The recessed air curtains ACA-DX-HP-GVP are equipped with EC fans and are specially designed for connection to Fujitsu inverter heat pumps with direct expansion. The sleek and modern air curtain is designed for use in shops and public areas where users do not want to worry about the air curtain and where maintaining high energy efficiency and comfort levels is required.
The ACA-DX-HP-GVP is available in three different capacities for door heights up to 3 m. The 3 lengths can be combined to provide a solution for every door width.
This type of air curtain is equipped with an ultramodern bypass system, which creates a pleasant air jet even during the inevitable defrost cycle of the heat pump, without consuming extra energy.
The air curtain is standard equipped with a wired control that makes it possible to control the ventilation speed in 5 positions and that is equipped with a door contact indication, various LED indicators, an automatic/manual mode and an on/off button for heating. The power supply board is also equipped with a GBS input (potential-free contact) and GBS output (potential-free contact) for external control.
Application
Hospitals
Shops
Office buildings
Hotel lobbies
Specifications
Only heating
Cooling on request
EC fans
Material
Steel casing.
Remote control in a PVC casing for mounting on a surface. Dimensions : 70x70x26mm.
Colour
RAL 9016 (traffic white). Other colors available on request
Mounting
Suited for recessed mounting in the ceiling
Accessoires
Communication module, type ACA-DX-BOX
Door contact
Connection to GBS by use of an external contact
Master/Slave control possible with RJ45 cable. Max. 30 m. (to provide on site)
Text for tender
The recessed air curtain has a state of the art bypass system, which creates a pleasant air jet even during the inevitable defrost cycle of the heat pump, without consuming extra energy. Thanks to this system, the air flow during the defrost cycle is not directed through the cold heat exchanger of the air curtain, but through the suction at the top of the air curtain. This temporarily uses the unused heat from the ceiling area to effectively shield the opening. After the heat pump has completed the defrost cycle, the air flow in the air curtain is returned to the heat exchanger.
The fan is controlled by a 5-speed remote control, supplied with the air curtain. This type of air curtain is only suitable for heat pump applications with Fujitsu inverter controlled outdoor units. The housing is painted in steel in RAL 9016, other colors are available on request. Up to 9 air curtains can be controlled in master/slave using an RJ45 cable and a wired control. This air curtain is GBS-ready and standard equipped with an external input contact, a door input contact and an operation and error output contact.
The recessed air curtain has a state of the art bypass system, which creates a pleasant air jet even during the inevitable defrost cycle of the heat pump, without consuming extra energy. Thanks to this system, the air flow during the defrost cycle is not directed through the cold heat exchanger of the air curtain, but through the suction at the top of the air curtain. This temporarily uses the unused heat from the ceiling area to effectively shield the opening. After the heat pump has completed the defrost cycle, the air flow in the air curtain is returned to the heat exchanger.
The fan is controlled by a 5-speed remote control, supplied with the air curtain. This type of air curtain is only suitable for heat pump applications with Fujitsu inverter controlled outdoor units. The housing is painted in steel in RAL 9016, other colors are available on request. Up to 9 air curtains can be controlled in master/slave using an RJ45 cable and a wired control. This air curtain is GBS-ready and standard equipped with an external input contact, a door input contact and an operation and error output contact.
Articles
Article selection assistant
Type
Article number
Type
E-shop
J110502700100
EBERLE 7001
=> Stock product central warehouse, except sales
=> Stock product local warehouses, except sales
Technical data
Recessed series type "HP-GVP"*
12
18
24
Length
cm
100
150
200
250
100
150
200
250
100
150
200
250
Mounting heigth (Max.)
m
< 2,30
< 2,60
< 3,00
Dimensions (HxL)°
mm
300x750
Outlet range
+30°/-30°
Air flow data of air curtain
Effective air fow rate
m³/h
1400
1800
2700
3600
1800
2700
3600
4500
2700
3600
5400
6300
Sound pressure level**
dB(A)
40-54
41-56
41-58
41-60
41-54
43-56
44-58
45-60
40-54
41-56
41-58
41-60
Weight
kg
61
71
93
135
61
74
960
138
65
78
104
145
Electrical data of fans
Power supply (50 Hz)°°
V
230/1
Absorbed power (Max.)
kW
0,33
0,33
0,5
0,66
0,33
0,54
0,66
0,83
0,52
0,66
0,99
1,16
Absorbed current (Max.)
A
2,4
2,4
3,6
4,8
2,4
3,6
4,8
6,0
3,6
4,8
7,2
8,4
Power cable section
mm²
3G 2,5
Automatic fuse (Slow)
A
10
Technical data of DX battery (H)
Heating capacity @ 20/35°C***
kW
6,9
9,3
13,4
18,7
9,1
13,4
18,2
22,3
12,2
17,9
27,2
32,3
Refrigerant
R410A
Battery diameter
inch
1/2-5/8
1/2-7/8
1/2-5/8
1/2-7/8
Technical data of matching Fujitsu outdoor unit
Type of unit (AOYG/A)
30 LETL
36 LETL
45 LATT
60 LATT
36 LETL
45 LATT
60 LATT
72 LRLA
36 LATT
60 LATT
72 LRLA
90 LRLA
Type of ACA-DX-BOX
ACA-DX-BOX 30
ACA-DX-BOX 36
ACA-DX-BOX 45
ACA-DX-BOX 60
ACA-DX-BOX 36
ACA-DX-BOX 45
ACA-DX-BOX 60
ACA-DX-BOX 72
ACA-DX-BOX 36
ACA-DX-BOX 60
ACA-DX-BOX 72
-
Power supply
V
230/1
400/3
230/1
400/3
Absorbed capacity (Nom. - Max.)
kW
2,68-3,8
3,1-4,5
3,8-5,8
5,1-7,1
3,1-4,5
3,8-5,8
5,1-7,1
6,2-9,8
2,8-5,1
5,1-7,1
6,2-9,8
8,2-12,1
Absorbed current (Nom. - Max.)
A
11,7-17
13,6-20
5,5-11
7,6-12,5
13,6-2
5,5-11
7,6-12,5
9,6-22,8
4,4-8,5
7,6-12,5
9,6-22,8
12-25,8
Dimemsions (Heigth)
mm
830
830
1290
1290
830
1290
1290
1690
1290
1290
1690
1690
Dimnsions (Length)
mm
900
900
900
900
900
900
900
930
900
900
930
930
Dimensions (Depth)
mm
330
330
330
330
330
330
330
765
330
330
765
765
Sound pressure level
dB(A)
55
55
54
56
55
54
56
57
53
56
57
59
Weight
kg
61
61
104
104
61
104
104
215
104
104
215
215
Cooling pipes1
inch
3/8-5/8
1/2-7/8
3/8-5/8
1/2-7/8
Amount of prefilled refrigerant
g
2100
2100
3450
3450
2100
3450
3450
11200
3450
3450
11200
11200
Extra amount of refrigerant
g/m
40
40
50
50
40
50
50
110
50
50
110
110
Number of prefilled meters
m
4
0
2
0
4
9
0
5
17
9
7,5
5
Maximum length/heigth of cooling pipes²
m
40/20
30/30
45/30
40/30
40/30
65/30
50/30
65/30
75/30
65/30
70/30
65/30
Minimum length of cooling pipes
m
5
5
5
5
5
5
5
5
5
5
5
5
Cable section between air curtain and outdoor unit
mm²
4G 1,5
Power cable section
mm²
3G 4
3G 4
5G 2,5
5G 2,5
3G 4
5G 2,5
5G 2,5
5G 4
5G 2,5
5G 2,5
5G 4
5G 4
Automatic fuse (Slow)
A
25
25
16
16
25
16
16
25
16
16
25
25
* Specifications and design are subject to change for further improvement without prior notice
** = The sound pressure level is measured at 3m distance of the air curtain's air intake at high speed
*** = Heating capacity at 20°C air intake temperature and 35°C air outlet temperature at a condensation temperature between 43 and 50°C
° = Fan connection on the left side when standing in front of the device
1 = Always use the same cooling pipes as the outdoor unit
Technical data
Refill (gr) *
12-1000 R
12-1500 R
12-2000 R
12-2500 R
18-1000 R
18-1500 R
18-2000 R
18-2500 R
18-1000 R
18-1500 R
18-2000 R
18-2500 R
Type of outdoor unit
30 LETL
36 LETL
45 LATT
60 LATT
36 LETL
45 LATT
60 LATT
72 LRLA
36 LATT
60 LATT
72 LRLA
90 LRLA
5m
30
430
140
410
30
x
140
x
x
x
x
x
10m
230
630
390
660
230
30
390
560
x
30
290
560
15m
430
830
640
910
430
280
640
1110
x
280
840
1110
20m
630
1030
890
1160
630
530
890
1660
130
530
1390
1660
25m
830
1230
1140
1410
830
780
1140
2210
380
780
1940
2210
30m
1030
1430
1390
1660
1030
1030
1390
2760
630
1030
2490
2760
35m
1230
-
1640
1910
1230
1280
1640
3310
880
1280
3040
3310
40m
1430
-
1890
2160
1430
1530
1890
3860
1130
1530
3590
3860
45m
-
-
2140
-
-
1780
2140
4410
1380
1780
4140
4410
50m
-
-
-
-
-
2030
2390
4960
1630
2030
4690
4960
55m
-
-
-
-
-
2280
-
5510
1880
2280
5240
5510
60m
-
-
-
-
-
2530
-
6060
2130
2530
5790
6060
65m
-
-
-
-
-
2780
-
6610
2380
2780
6340
6610
70m
-
-
-
-
-
-
-
-
2630
-
6890
-
75m
-
-
-
-
-
-
-
-
2880
-
-
-
gr/m
40
40
50
50
40
50
40
110
50
50
110
110
x = No extra refill required
- = Unauthorized length of cooling pipes still possible for this combination
* = Minimum 5m of cooling pipes between the air curtain and the Fujitsu outdoor unit