Air curtain with a modern casing with a length of 1 m, 1.5 m or 2 m for door heights up to 4 m. Available in versions with electric (E) or hot water coil (W) or without heating (N). The installation of a S-TOUCH control via an external control module S-ECM is strongly recommended to ensure the proper functioning of the air curtain..

Application

  • Used in offices and industrial buildings where a clean design is required. SOLANO DESIGN curtains are dedicated for horizontal installation directly above the door.

Specifications

  • 3-speed motor
  • Adjustable air stream
  • Crossflow fan
  • Vertical mounting
  • 4,0-meter range*
  • Air inlet on the upper side
  • Controlled by thermostat with speed controller
  • Door switch operation
  • BMS connection possible
*Vertical range of isothermal stream (at velocity boundary equal to 2,0 m/s)

Accessoires

  • Touchscreen control, type S-TOUCH
  • External control module, type S-ECM
  • Brackets for SOLANO DESIGN, type S-UB
  • Room thermostat for SOLANO, type S-C
  • Motorised hydraulic valve, QCV-2* and QCV-3*
* only to be used in combination with S-ECM
  • Motorised hydraulic valve, S-V-2 and S-V-3

Technical data

  Design W-100Design N-100Design E-100Design W-150Design N-150Design E-150Design W-200Design N-200Design E-200
Power supply[V/Hz]230/50230/503 x 400/50230/50230/503x400/50230/50230/503x400/50
Power consumption[kW]0.360.47.50.460.4811.50.50.5415.5
Current consumption[A]1.71.9112.12.116.62.32.422.4
Heating capacity[kW]13.6 -723 -1130.8 -15
IP 212121212121212121
Connection["]1/2" - -1/2" - -1/2" - -
Air flow[m³/h]290033002900430050004300550063005500
Sound level (1)[dB(A)]596059606160606160
Max. heating water temp.[°C]95 - -95 - -95 - -
Max. operating pressure[MPa]1.6 - -1.6 - -1.6 - -
Air temperature rise (2)(∆T) [°C]14 -1116 -1217 -13
Weight[kg]25.8242832.930.734.939.236.341.9
(1) Conditions: distance to the unit 3 metres at 500 m³ and medium room sound absorption, second Fan step
(2) Inlet/outlet water temperature 90/70°C and inlet air temperature 10°C

Order example

DESIGN W-100
W = curtain with water heater exchanger
N = curtain without heater exchanger (ambient)
E = curtain with electric heaters

Dimensions

 Design 100Design 150Design 200
A [mm]605605605
B [mm]555555555
C [mm]280280280
D [mm]707070
E [mm]255255255
F [mm]300300300
G [mm]105515452035