Transmitters for measuring carbon dioxide levels in the extraction channel. They feature an analogue signal 0-10V and a built-in relay with switching output.
Brand
Regin
Application
For regulation of ventilation systems in function of the CO2 concentration
Mounting
Appropriate for duct mounting
Accessoires
Transfo 230 / 24 V AC,type TRAFO 15/D
Technical data
Supply voltage: 24V AC/DC ±10%
Measuring range CO2 : 0 - 2000 or 0-5000 ppm
Outputs: 0-10V or 4-20mA and relay 24V (max 1A)
Measuring range temperature : -10 - 60°C
Accuracy CO2 : ± 30 ppm (±3% of the measured value)
Measuring principle CO2 : NDIR (Non-dispersive infrared technology)