The globe valve has been designed for use in stationary heating, ventilation and
air-conditioning systems and is not allowed to be used outside the specified field
of application, especially in aircraft or in any other airborne means of transport.
Specifications
The globe valve is adjusted by a globe valve actuator. The actuators are connected by a commercially available modulating or 3-point control system and move the valve cone, which acts as a throttling device, into the opening position dictated by the positioning signal. Coupling pipes not included!
Articles
Article selection assistant
Type
U [V]
Integrated auxiliary switch
Article number
Type
U [V]
Integrated auxiliary switch
E-shop
J120521024001
EF 24A
24
No
J120521024021
EF 24A-S2
24
Yes
J120521230001
EF 230A
230
No
J120521230021
EF 230A-S2
230
Yes
Specifications
DN [mm]
Rp [Inch]
Kvs [m³/h]
ps [kPa]
Stroke [mm]
H511B
15
1/2
0,63
1600
15
H512B
15
1/2
1
1600
15
H513B
15
1/2
1,6
1600
15
H514B
15
1/2
2,5
1600
15
H515B
15
1/2
4
1600
15
H520B
20
3/4
6,3
1600
15
H525B
25
1
10
1600
15
H532B
32
1 1/4
16
1600
15
Technical data
Functional data
Media: Cold and hot water, water with glycol up to max. 50% vol
Medium temperature: 5°C ... 120 °C
Leakage rate: Leakage Class III (DIN EN 1349 and DIN EN 60534-4
Pipe connectors: External thread in accordance to ISO 228
Closing point: Top
Installation position: Upright to horizontal (in relation to the stem)