This site uses cookies and related technologies, as described in our privacy policy, for purposes that may include site operation, analytics, enhanced user experience, or advertising. You may choose to consent to our use of these technologies, or manage your own preferences.
The globe valve has been designed for use in stationary heating, ventilation and
air-conditioning systems and is not allowed to be used outside the specified field
of application, especially in aircraft or in any other airborne means of transport.
Specifications
The globe valve is adjusted by a globe valve actuator. The actuators are connected by a commercially available modulating or 3-point control system and move the valve cone, which acts as a throttling device, into the opening position dictated by the positioning signal. Coupling pipes not included!
Articles
Article selection assistant
Diameter D [mm]
Article number
Type [mm]
Diameter D [mm]
E-shop
C010324080000
BDSG 30 80
80
C010324100000
BDSG 30 100
100
C010324125000
BDSG 30 125
125
C010324150000
BDSG 30 150
150
C010324160000
BDSG 30 160
160
C010324180000
BDSG 30 180
180
C010324200000
BDSG 30 200
200
C010324250000
BDSG 30 250
250
C010324315000
BDSG 30 315
315
C010324355000
BDSG 30 355
355
C010324400000
BDSG 30 400
400
C010324450000
BDSG 30 450
450
C010324500000
BDSG 30 500
500
C010324560000
BDSG 30 560
560
C010324630000
BDSG 30 630
630
C010324710000
BDSG 30 710
710
C010324800000
BDSG 30 800
800
=> Stock product central warehouse, except sales
=> Stock product local warehouses, except sales
Specifications
DN [mm]
Rp [Inch]
Kvs [m³/h]
ps [kPa]
Stroke [mm]
H511B
15
1/2
0,63
1600
15
H512B
15
1/2
1
1600
15
H513B
15
1/2
1,6
1600
15
H514B
15
1/2
2,5
1600
15
H515B
15
1/2
4
1600
15
H520B
20
3/4
6,3
1600
15
H525B
25
1
10
1600
15
H532B
32
1 1/4
16
1600
15
Technical data
Functional data
Media: Cold and hot water, water with glycol up to max. 50% vol
Medium temperature: 5°C ... 120 °C
Leakage rate: Leakage Class III (DIN EN 1349 and DIN EN 60534-4
Pipe connectors: External thread in accordance to ISO 228
Closing point: Top
Installation position: Upright to horizontal (in relation to the stem)