Diffuseurs plafonniers circulaires multibuses à haute induction avec buses individuellement règlables à placement circulaire, à prévoir d'un caisson en acier galvanisé.
- CNC-1A, 600 + RER-B 600 + CRC 250
Explication
CNC-1A = Type de diffuseur
600 = Dimension du diffuseur
Accessoires
RER-B = Type de caisson
600 = Dimension du de caisson
CRC = Clapet de réglage pour caisson
250 = Diamètre de connexion du caisson
Dimensions
|
300 | 300 | 22 | 400 | 400 | 42 | 500 | 500 | 68 | 600 | 600 | 100 | 625* | 625 | 100 | * niet meer verkrijgbaar / n'est plus disponible / no longer available |
Sélection rapide
|
Q | Ak | 0.0057 | 0.0114 | 0.0153 | 0.0258 | |
50 | | H= | 2.7 | 0.3 | 0.12 | 0.06 | 0.25 | 0.1 | 0.05 | | | | | | | Vz | H= | 3.2 | 0.14 | 0.07 | 0.04 | 0.12 | 0.06 | 0.03 | | | | | | | | H= | 3.8 | 0.07 | 0.04 | 0.02 | 0.06 | 0.03 | 0.02 | | | | | | | Vk | 2.4 | 1.2 | | | X0,25 | 1.6 | 1.5 | | | Ps | 6 | 2 | | | Lw(A) | 24 | <20 | | | 75 | | H= | 2.7 | 0.42 | 0.19 | 0.11 | 0.34 | 0.15 | 0.08 | 0.32 | 0.14 | 0.08 | | | | Vz | H= | 3.2 | 0.22 | 0.12 | 0.07 | 0.17 | 0.09 | 0.06 | 0.16 | 0.08 | 0.05 | | | | | H= | 3.8 | 0.12 | 0.07 | 0.05 | 0.09 | 0.06 | 0.04 | 0.08 | 0.05 | 0.03 | | | | Vk | 3.7 | 1.8 | 1.4 | | X0,25 | 1.8 | 1.7 | 1.6 | | Ps | 13 | 4 | 2 | | Lw(A) | 33 | <20 | <20 | | 100 | | H= | 2.7 | 0.53 | 0.27 | 0.16 | 0.42 | 0.2 | 0.12 | 0.38 | 0.18 | 0.1 | 0.3 | 0.13 | 0.07 | Vz | H= | 3.2 | 0.29 | 0.17 | 0.11 | 0.22 | 0.13 | 0.08 | 0.2 | 0.11 | 0.07 | 0.15 | 0.08 | 0.05 | | H= | 3.8 | 0.17 | 0.11 | 0.08 | 0.13 | 0.08 | 0.05 | 0.11 | 0.07 | 0.05 | 0.08 | 0.05 | 0.03 | Vk | 4.9 | 2.4 | 1.8 | 1.1 | X0,25 | 2.1 | 1.9 | 1.8 | 1.6 | Ps | 24 | 7 | 4 | 2 | Lw(A) | 38 | 23 | <20 | <20 | 150 | | H= | 2.7 | | | | 0.58 | 0.3 | 0.19 | 0.51 | 0.26 | 0.16 | 0.39 | 0.18 | 0.11 | Vz | H= | 3.2 | | | | 0.33 | 0.2 | 0.14 | 0.29 | 0.17 | 0.11 | 0.21 | 0.12 | 0.07 | | H= | 3.8 | | | | 0.2 | 0.14 | 0.1 | 0.17 | 0.11 | 0.08 | 0.12 | 0.07 | 0.05 | Vk | | 3.7 | 2.7 | 1.6 | X0,25 | | 2.3 | 2.1 | 1.8 | Ps | | 16 | 9 | 3 | Lw(A) | | 33 | 27 | <20 | 200 | | H= | 2.7 | | | | 0.71 | 0.4 | 0.26 | 0.63 | 0.34 | 0.22 | 0.49 | 0.25 | 0.15 | Vz | H= | 3.2 | | | | 0.43 | 0.28 | 0.19 | 0.37 | 0.23 | 0.16 | 0.27 | 0.16 | 0.11 | | H= | 3.8 | | | | 0.28 | 0.19 | 0.14 | 0.23 | 0.16 | 0.12 | 0.16 | 0.11 | 0.08 | Vk | | 4.9 | 3.6 | 2.2 | X0,25 | | 2.7 | 2.4 | 2 | Ps | | 28 | 16 | 6 | Lw(A) | | 40 | 34 | 23 | 250 | | H= | 2.7 | | | | | | | 0.74 | 0.42 | 0.28 | 0.57 | 0.3 | 0.19 | Vz | H= | 3.2 | | | | | | | 0.46 | 0.3 | 0.21 | 0.33 | 0.2 | 0.14 | | H= | 3.8 | | | | | | | 0.3 | 0.21 | 0.16 | 0.2 | 0.14 | 0.1 | Vk | | | 4.5 | 2.7 | X0,25 | | | 2.8 | 2.3 | Ps | | | 25 | 9 | Lw(A) | | | 40 | 28 | 300 | | H= | 2.7 | | | | | | | 0.85 | 0.5 | 0.34 | 0.64 | 0.35 | 0.23 | Vz | H= | 3.2 | | | | | | | 0.54 | 0.36 | 0.26 | 0.39 | 0.24 | 0.17 | | H= | 3.8 | | | | | | | 0.36 | 0.26 | 0.2 | 0.24 | 0.17 | 0.12 | Vk | | | 5.4 | 3.2 | X0,25 | | | 3.2 | 2.5 | Ps | | | 35 | 13 | Lw(A) | | | 45 | 33 | 350 | | H= | 2.7 | | | | | | | | | | 0.73 | 0.42 | 0.27 | Vz | H= | 3.2 | | | | | | | | | | 0.45 | 0.29 | 0.21 | | H= | 3.8 | | | | | | | | | | 0.29 | 0.21 | 0.16 | Vk | | | | 3.8 | X0,25 | | | | 2.8 | Ps | | | | 18 | Lw(A) | | | | 37 | 400 | | H= | 2.7 | | | | | | | | | | 0.79 | 0.47 | 0.31 | Vz | H= | 3.2 | | | | | | | | | | 0.51 | 0.33 | 0.24 | | H= | 3.8 | | | | | | | | | | 0.33 | 0.24 | 0.18 | Vk | | | | 4.3 | X0,25 | | | | 3 | Ps | | | | 23 | Lw(A) | | | | 41 | 450 | | H= | 2.7 | | | | | | | | | | 0.86 | 0.52 | 0.36 | Vz | H= | 3.2 | | | | | | | | | | 0.56 | 0.38 | 0.28 | | H= | 3.8 | | | | | | | | | | 0.38 | 0.28 | 0.21 | Vk | | | | 4.8 | X0,25 | | | | 3.3 | Ps | | | | 29 | Lw(A) | | | | 44 |
Symboles et spécifications
- Q = Débit d'air en m³/h
- Ak = Surface efffective (passage libre) en m²
- B = Distance entre diffuseurs en m
- H = Hauteur de placement en m
- Vz = Vitesse maximale à la zone d'occupation en fonction de la distance entre les diffuseurs et la hauteur de placement en m/s
- Vk = Vitesse réelle à travers le diffuseur en m/s
- X0.25 = Portée horizontale en m à une vitesse finale Vt de 0,25m/s
- Ps = Perte de pression statique du diffuseur en Pa
- Lw(A) = Puissance acoustique du diffuseur en dB(A)
- La portée X0.25 est donnée à une vitesse finale Vt de 0,25 m/s pour un plafond lisse sans obstacles.
- Les valeurs sont données en condition isothermique de l'air. Les portées pour des conditions en refroidissement à -11K doivent être recalculées en divisant les valeurs de X0.25 par le facteur 1,1. En chauffage à Dt 11K, les valeurs doivent être recalculées en multipliant X0.25 par le facteur 1,1.
- Pour atteindre un niveau élevé de confort, vous pouvez faire une sélection basée sur la vitesse maximale de l'air dans la zone d'occupation Vz. Ces valeurs sont données à des distances B entre les diffuseurs et les hauteurs d'installation H. Des vitesses Vz inférieures, ou égales à 0,25 m/s sont conseillées dans la zone d'occupation.
- Les pertes de pression Ps sont données pour des diffuseurs sans registre ou avec registre totalement ouvert.
- Les puissances acoustiques Lw(A) sont données pour des diffuseurs sans registre ou avec registre totalement ouvert sans atténuation de la chambre. Puissances acoustiques inférieures à 20 dB(A) sont indiquées comme "<20" dans les tableaux.
- Pour toutes les exigences particulières, veuillez contacter notre bureau d'étude.