Diffuseurs plafonniers carrés multibuses à haute induction avec buses individuellement règlables à placement carré, à prévoir d'un caisson en acier galvanisé.
PS/SNS-1A = grille SNS-1A dans une dalle 596 X 596
- SNS-1A RAL9005, 600 + REV-B 600 + CRC 250
Explication
SNS-1A RAL9005 = Type de diffuseur
600 = Dimension du diffuseur
Accessoires
REV-B = Type de caisson
600 = Dimension du caisson
CRC = Clapet de réglage pour caisson
250 = Diamètre de connexion du caisson
Dimensions
|
SNS-1A 300-36 | 296x296 | 36 | SNS-1A 400-64 | 396x396 | 64 | SNS-1A 500-80 | 496x496 | 80 | SNS-1A 600-100 | 596x596 | 100 | SNS-1A 600-144 | 596x596 | 144 | SNS-1A 625-100* | 621x621 | 100 | PS/SNS-1A 300/596-36 | 596x596 | 36 | PS/SNS-1A 400/596-64 | 596x596 | 64 | PS/SNS-1A 500/596-80 | 596x596 | 80 | * niet meer verkrijgbaar / n'est plus disponible / no longer available |
Sélection rapide
|
| Ak | 0.0093 | 0.0165 | 0.0206 | 0.0258 | 0.0372 | |
75 | | H= | 2.7 | 0.42 | 0.2 | 0.12 | 0.38 | 0.18 | 0.11 | 0.35 | 0.17 | 0.1 | | | | | | | Vz | H= | 3.2 | 0.23 | 0.13 | 0.08 | 0.2 | 0.12 | 0.07 | 0.19 | 0.1 | 0.07 | | | | | | | | H= | 3.8 | 0.13 | 0.08 | 0.06 | 0.12 | 0.07 | 0.05 | 0.1 | 0.07 | 0.05 | | | | | | | Vk | 2.2 | 1.3 | 1 | | | | | X0,25 | 1.9 | 1.8 | 1.7 | | | | | Ps | 5 | 2 | 1 | | | | | Lw(A) | 21 | <20 | <20 | | | | | 100 | | H= | 2.7 | 0.53 | 0.27 | 0.17 | 0.46 | 0.23 | 0.14 | 0.42 | 0.21 | 0.12 | 0.37 | 0.18 | 0.11 | | | | Vz | H= | 3.2 | 0.3 | 0.18 | 0.12 | 0.26 | 0.15 | 0.1 | 0.23 | 0.13 | 0.09 | 0.2 | 0.11 | 0.07 | | | | | H= | 3.8 | 0.18 | 0.12 | 0.08 | 0.15 | 0.1 | 0.07 | 0.13 | 0.09 | 0.06 | 0.11 | 0.07 | 0.05 | | | | Vk | 3 | 1.7 | 1.3 | 1.1 | | | | X0,25 | 2.1 | 2 | 1.9 | 1.8 | | | | Ps | 10 | 4 | 2 | 2 | | | | Lw(A) | 28 | <20 | <20 | <20 | | | | 150 | | H= | 2.7 | 0.72 | 0.4 | 0.26 | 0.6 | 0.33 | 0.21 | 0.57 | 0.31 | 0.19 | 0.49 | 0.25 | 0.15 | 0.38 | 0.18 | 0.11 | Vz | H= | 3.2 | 0.44 | 0.28 | 0.2 | 0.36 | 0.22 | 0.15 | 0.34 | 0.21 | 0.14 | 0.28 | 0.17 | 0.11 | 0.2 | 0.12 | 0.07 | | H= | 3.8 | 0.28 | 0.2 | 0.15 | 0.22 | 0.15 | 0.11 | 0.21 | 0.14 | 0.1 | 0.17 | 0.11 | 0.08 | 0.12 | 0.07 | 0.05 | Vk | 4.5 | 2.5 | 2 | 1.6 | 1.1 | X0,25 | 2.7 | 2.4 | 2.3 | 2.1 | 1.8 | Ps | 22 | 8 | 5 | 3 | 2 | Lw(A) | 37 | 25 | <20 | <20 | <20 | 200 | | H= | 2.7 | | | | 0.75 | 0.43 | 0.28 | 0.7 | 0.4 | 0.26 | 0.61 | 0.33 | 0.21 | 0.46 | 0.24 | 0.14 | Vz | H= | 3.2 | | | | 0.47 | 0.3 | 0.21 | 0.43 | 0.28 | 0.2 | 0.36 | 0.23 | 0.16 | 0.26 | 0.15 | 0.1 | | H= | 3.8 | | | | 0.3 | 0.21 | 0.16 | 0.28 | 0.2 | 0.15 | 0.23 | 0.16 | 0.12 | 0.15 | 0.1 | 0.07 | Vk | | 3.4 | 2.7 | 2.2 | 1.5 | X0,25 | | 2.8 | 2.7 | 2.4 | 2 | Ps | | 14 | 9 | 6 | 3 | Lw(A) | | 33 | 28 | 23 | <20 | 250 | | H= | 2.7 | | | | 0.87 | 0.52 | 0.35 | 0.83 | 0.49 | 0.33 | 0.7 | 0.4 | 0.26 | 0.54 | 0.29 | 0.18 | Vz | H= | 3.2 | | | | 0.56 | 0.37 | 0.27 | 0.53 | 0.35 | 0.25 | 0.43 | 0.28 | 0.2 | 0.32 | 0.19 | 0.13 | | H= | 3.8 | | | | 0.37 | 0.27 | 0.21 | 0.35 | 0.25 | 0.19 | 0.28 | 0.2 | 0.15 | 0.19 | 0.13 | 0.1 | Vk | | 4.2 | 3.4 | 2.7 | 1.9 | X0,25 | | 3.3 | 3.1 | 2.7 | 2.2 | Ps | | 21 | 14 | 9 | 4 | Lw(A) | | 38 | 34 | 28 | <20 | 300 | | H= | 2.7 | | | | | | | 0.93 | 0.56 | 0.39 | 0.79 | 0.46 | 0.31 | 0.62 | 0.34 | 0.22 | Vz | H= | 3.2 | | | | | | | 0.61 | 0.41 | 0.3 | 0.5 | 0.33 | 0.24 | 0.37 | 0.23 | 0.16 | | H= | 3.8 | | | | | | | 0.41 | 0.3 | 0.24 | 0.33 | 0.24 | 0.18 | 0.23 | 0.16 | 0.12 | Vk | | | 4 | 3.2 | 2.2 | X0,25 | | | 3.5 | 3 | 2.4 | Ps | | | 20 | 13 | 6 | Lw(A) | | | 39 | 33 | 23 | 350 | | H= | 2.7 | | | | | | | 1.04 | 0.65 | 0.46 | 0.89 | 0.54 | 0.37 | 0.69 | 0.39 | 0.25 | Vz | H= | 3.2 | | | | | | | 0.7 | 0.48 | 0.36 | 0.58 | 0.39 | 0.29 | 0.42 | 0.27 | 0.19 | | H= | 3.8 | | | | | | | 0.48 | 0.36 | 0.29 | 0.39 | 0.29 | 0.22 | 0.27 | 0.19 | 0.14 | Vk | | | 4.7 | 3.8 | 2.6 | X0,25 | | | 4 | 3.4 | 2.6 | Ps | | | 28 | 18 | 9 | Lw(A) | | | 43 | 37 | 27 | 400 | | H= | 2.7 | | | | | | | | | | 0.97 | 0.6 | 0.42 | 0.75 | 0.44 | 0.29 | Vz | H= | 3.2 | | | | | | | | | | 0.65 | 0.44 | 0.33 | 0.47 | 0.31 | 0.22 | | H= | 3.8 | | | | | | | | | | 0.44 | 0.33 | 0.26 | 0.31 | 0.22 | 0.17 | Vk | | | | 4.3 | 3 | X0,25 | | | | 3.7 | 2.9 | Ps | | | | 23 | 11 | Lw(A) | | | | 41 | 31 | 450 | | H= | 2.7 | | | | | | | | | | 1.05 | 0.66 | 0.47 | 0.82 | 0.48 | 0.33 | Vz | H= | 3.2 | | | | | | | | | | 0.71 | 0.49 | 0.37 | 0.52 | 0.35 | 0.25 | | H= | 3.8 | | | | | | | | | | 0.49 | 0.37 | 0.29 | 0.35 | 0.25 | 0.19 | Vk | | | | 4.8 | 3.4 | X0,25 | | | | 4.1 | 3.1 | Ps | | | | 29 | 14 | Lw(A) | | | | 44 | 34 | 500 | | H= | 2.7 | | | | | | | | | | | | | 0.88 | 0.53 | 0.36 | Vz | H= | 3.2 | | | | | | | | | | | | | 0.57 | 0.39 | 0.28 | | H= | 3.8 | | | | | | | | | | | | | 0.39 | 0.28 | 0.22 | Vk | | | | | | | | | | | | | 3.7 | X0,25 | | | | | | | | | | | | | 3.4 | Ps | | | | | | | | | | | | | 17 | Lw(A) | | | | | | | | | | | | | 37 | 600 | | H= | 2.7 | | | | | | | | | | | | | 1 | 0.62 | 0.44 | Vz | H= | 3.2 | | | | | | | | | | | | | 0.67 | 0.46 | 0.34 | | H= | 3.8 | | | | | | | | | | | | | 0.46 | 0.34 | 0.27 | Vk | | | | | | | | | | | | | 4.5 | X0,25 | | | | | | | | | | | | | 3.9 | Ps | | | | | | | | | | | | | 25 | Lw(A) | | | | | | | | | | | | | 42 |
Symboles et spécifications
- Q = Débit d'air en m³/h
- Ak = Surface effective (passage libre) en m²
- B = Distance entre diffuseurs en m
- H = Hauteur de placement en m
- Vz = Vitesse maximale à la zone d'occupation en fonction de la distance entre les diffuseurs et la hauteur de placement en m/s
- Vk = Vitesse réelle à travers le diffuseur en m/s
- X0.25 = Portée horizontale en m à une vitesse finale Vt de 0,25m/s
- Ps = Perte de pression statique du diffuseur en Pa
- Lw(A) = Puissance acoustique du diffuseur en dB(A)
- La portée X0.25 est donnée à une vitesse finale Vt de 0,25 m/s pour un plafond lisse sans obstacles.
- Les valeurs sont données en condition isothermique de l'air. Les portées pour des conditions en refroidissement à -11K doivent être recalculées en divisant les valeurs de X0.25 par le facteur 1,1. En chauffage à Dt 11K, les valeurs doivent être recalculées en multipliant X0.25 par le facteur 1,1.
- Pour atteindre un niveau élevé de confort, vous pouvez faire une sélection basée sur la vitesse maximale de l'air dans la zone d'occupation Vz. Ces valeurs sont données à des distances B entre les diffuseurs et les hauteurs d'installation H. Des vitesses Vz inférieures, ou égales à 0,25 m/s sont conseillées dans la zone d'occupation.
- Les pertes de pression Ps sont données pour des diffuseurs sans registre ou avec registre totalement ouvert.
- Les puissances acoustiques Lw(A) sont données pour des diffuseurs sans registre ou avec registre totalement ouvert sans atténuation de la chambre. Puissances acoustiques inférieures à 20 dB(A) sont indiquées comme "<20" dans les tableaux.
- Pour toutes les exigences particulières, veuillez contacter notre bureau d'étude.
Placement des diffuseurs
|