PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

ALG-0 • Aluminium linear wall grilles

Anodized aluminium grilles with fixed blades and a blade pitch of 12.5 mm, deflection 0°

Brand

  • Cairox

Application

  • Used for air supply and air exhaust in ventilation and air conditioning systems

Material

  • Aluminium

Colour

  • Anodized natural finish
  • Other colours available upon request

Composition

  • Deflection: fixed 0°
  • Single row of horizontal blades

Mounting

  • Invisible mounting with clips in mounting frame, type CCN

Accessories

  • Mounting frame for clip fixing, type CCN
  • Volume control damper, type DWN
  • Plenum box, type REW
  • Insulating plenum box, type REW ISO

Other available products

  • ALG-15 with 15° deflection

Text for tender

Copy
  • The air supply wall grilles have fixed blades with a clip fixing system and are supplied with a galvanised steel volume control damper.
  • Anodized natural aluminium
  • Cairox Type ALG-0+CCN+DWN+REW(ISO)

Order example

  • ALG-0, 800, 200 + CCN + DWN + REW

Explanation

ALG-0 = Grille type

800 = Length

200 = Height

Accessories (optional)

CCN = Mounting frame

DWN = Volume control damper

REW = Plenum box

Quick selection

ALG-0LxH
200x100300x100 400x100
300x150
200x200
500x100600x100
400x150
300x200
500x150800x100
400x200
600x150
300x300
500x200
1000x100
800x150
600x200
400x300
1000x150
800x200
500x300
600x3001000x200800x3001000x300
QAk0.00210.00830.01450.02060.02680.03610.03920.04530.05150.06380.08230.10080.11320.13790.1749
50Vk6.61.7             
X0,255.73.3             
Ps 322             
Lw(A)30<20             
100Vk 3.31.91.31          
X0,25 6.14.84.23.8          
Ps  8311          
Lw(A) 24<20<20<20          
150Vk 52.921.61.21.1        
X0,25 8.86.965.44.84.6        
Ps  1963211        
Lw(A) 3225<20<20<20<20        
200Vk 6.73.82.72.11.51.41.21.1      
X0,25 11.597.876.265.65.4      
Ps  3311632211      
Lw(A) 38302522<20<20<20<20      
300Vk  5.743.12.32.11.81.61.31    
X0,25  13.211.410.298.78.17.77.16.4    
Ps   24127443211    
Lw(A)  38333025242221<20<20    
400Vk  7.75.44.13.12.82.52.21.71.41.1   
X0,25  17.41513.311.711.310.610.19.28.37.6   
Ps   4221137654211   
Lw(A)  4439353130282623<20<20   
600Vk    6.24.64.33.73.22.621.71.51.2 
X0,25    19.717.316.715.614.813.512.111.110.59.7 
Ps     28161310853221 
Lw(A)    43393836343127252320 
800Vk     6.25.74.94.33.52.72.221.61.3
X0,25     22.82220.619.517.815.914.513.812.711.5
Ps      28241814964321
Lw(A)     44434139373330292623
1000Vk     7.77.16.15.44.43.42.82.521.6
X0,25     28.427.325.624.22219.71817.115.714.2
Ps      433627211496532
Lw(A)     49484644413735333027
1200Vk       7.46.55.24.13.32.92.41.9
X0,25       30.628.926.323.521.520.418.716.9
Ps        393020128753
Lw(A)       4947444138363430
1600Vk         75.44.43.93.22.5
X0,25         34.931.128.42724.722.3
Ps          3521141285
Lw(A)         504644423936
2000Vk          6.85.54.943.2
X0,25          38.735.433.630.827.7
Ps           332218128
Lw(A)          5148464440

Symbols and specifications

  • LxH = Width L and height H in mm

  • Q = Air volume in m³/h

  • Ak = Effective surface (free area) in m²

  • Vk = Average effective velocity through the grill in m/s

  • X0.25 = Horizontal throw in m at an endvelocity Vt of 0.25 m/s

  • Ps = Static pressure loss given in Pa

  • Lw(A) = Acoustic power in dB(A)


  • The throw X0.25 is given without deflection of the airstream at an end velocity of 0.25m/s. The distances are given for a smooth ceiling and installation distance of the center of the grille at 300mm from the ceiling surface. When mounted at a distance of 400 to 600 mm from the ceiling, a horizontal deflection towards the ceiling of 15° is advised. When mounted at a distance larger than 600mm from the ceiling, the throw distance X0.25 will be smaller than mentioned due to the missing coanda effect. In these cases and for all other special requirements, please contact our engineering office.

  • The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.

  • Advised mounting distance between centers of multiple grilles in the same wall should be greater than 1/3 of the throw length X0.25 (without spread)

  • The pressure losses Ps are given for grilles without damper of with fully opened damper.

  • The acoustic powers Lw(A) are given for grilles without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.

Placement instruction

HELPCopyrightSales conditionsCookie policyfujitsu-airco.be