Anodized aluminium floor grilles with fixed blade inner core and flat face. Grilles designed for installation in constructional floor openings, floor plenumboxes of steel or cast or screed processed plastic plenums of various manufactures.
Quick selection
|
Ak | 0.010 | 0.014 | 50 | Vk | 1.4 | | Ps | 2 | | Lw(A) | <10 | | X0.5
| 2 | | 75 | Vk | 2.1 | 1.5 | Ps | 5 | 2 | Lw(A) | 11 | <10 | X0.5
| 2.9 | 2.5 | 100 | Vk | 2.8 | 2.0 | Ps | 8 | 4 | Lw(A) | 18 | 10 | X0.5
| 3.9 | 3.3 | 125 | Vk | 3.5 | 2.5 | Ps | 13 | 6 | Lw(A) | 25 | 16 | X0.5
| 4.9 | 4.1 | 150 | Vk | 4.3 | 3.0 | Ps | 18 | 9 | Lw(A) | 30 | 21 | X0.5
| 5.9 | 4.9 | 200 | Vk | | 4.0 | Ps | | 16 | Lw(A) | | 29 | X0.5
| | 6.6 | 250 | Vk | | 5 | Ps | | 25 | Lw(A) | | 35 | X0.5
| | 8.2 |
Symbols and specifications
LxH = Width L en height H in mm - Q = Air volume in m³/h
Ak = Effective surface (free area) in m² Vk = Average effective velocity through the grill in m/s - Y0.5 = Vertical throw at an endvelocity Vt of 0.5 m/s
- Ps = Static pressure loss given in Pa
- Lw(A) = Acoustic power in dB(A)
- The values are given for isothermal supply air.
- The pressure losses Ps are given for grilles without damper of with fully opened damper.
- The acoustic power Lw(A) are given for grilles without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
- For all other special requirements, please contact our engineering office.
Placement instruction
|