Aluminium door or transfer grilles for placement in doors and walls from 30 upto 54 mm.
Grille with an average free area of 39%
Quick selection
|
Ak
| 0.0078
| 0.0117
| 0.0156
| 0.0195
| 0.0234
| 0.0312
| 0.0468
| 0.0585
| 0.0702
| 0.0936
| 60 | Vk | 2.14 | 1.42 | 1.07 | | | | | | | | Ps | 14.10 | 6.30 | 3.60 | | | | | | | | Lw(A) | 19 | 9 | 1 | | | | | | | | 80 | Vk | 2.85 | 1.90 | 1.42 | 1.14 | | | | | | | Ps | 25 | 11.10 | 6.30 | 4 | | | | | | | Lw(A) | 28 | 18 | 10 | 4 | | | | | | | 100 | Vk | 3.56 | 2.37 | 1.78 | 1.42 | 1.19 | 0.89 | | | | | Ps | 39.10 | 17.40 | 9.80 | 6.30 | 4.30 | 2.40 | | | | | Lw(A) | 35 | 24 | 17 | 11 | 6 | - | | | | | 150 | Vk | | 3.56 | 2.67 | 2.14 | 1.78 | 1.34 | | | | | Ps | | 39.10 | 22 | 14.10 | 9.80 | 5.50 | | | | | Lw(A) | | 37 | 29 | 23 | 19 | 11 | | | | | 200 | Vk | | | 3.56 | 2.85 | 2.37 | 1.78 | 1.19 | | | | Ps | | | 39.10 | 25 | 17.40 | 9.80 | 4.30 | | | | Lw(A) | | | 38 | 32 | 27 | 20 | 9 | | | | 250 | Vk | | | | 3.56 | 2.97 | 2.23 | 1.48 | 1.19 | | | Ps | | | | 39.10 | 27.20 | 15.30 | 6.80 | 4.30 | | | Lw(A) | | | | 39 | 34 | 27 | 16 | 10 | | | 300 | Vk | | | | | 3.56 | 2.67 | 1.78 | 1.42 | 1.19 | | Ps | | | | | 39.10 | 22 | 9.80 | 6.30 | 4.50 | | Lw(A) | | | | | 40 | 32 | 22 | 16 | 11 | | 400 | Vk | | | | | | 3.56 | 2.37 | 1.90 | 1.58 | 1.19 | Ps | | | | | | 39.10 | 17.40 | 11.10 | 7.70 | 4.30 | Lw(A) | | | | | | 41 | 30 | 25 | 20 | 12 | 500 | Vk | | | | | | | 2.97 | 2.37 | 1.98 | 1.48 | Ps | | | | | | | 27.20 | 17.40 | 12.10 | 6.80 | Lw(A) | | | | | | | 37 | 31 | 27 | 19 | 600 | Vk | | | | | | | 3.56 | 2.85 | 2.37 | 1.78 | Ps | | | | | | | 39.10 | 25 | 17.40 | 9.80 | Lw(A) | | | | | | | 43 | 37 | 32 | 25 |
Selection table
|
200 X 100 | 22 | 50 | 300 X 100 | 33 | 75 | 300 X 200 | 67 | 151 | 400 X 100 | 45 | 101 | 400 X 200 | 90 | 202 | 400 X 300 | 135 | 303 | 500 X 100 | 56 | 126 | 500 X 300 | 169 | 379 | 600 X 200 | 135 | 303 | 600 X 300 | 203 | 455 | 600 X 400 | 271 | 606 |
Symbols and specifications
- Ps = Static pressure loss in Pa
- Q = Air Volume in m³/h
- L x H = Hole in wall or door in mm
- Vk = Effective air velocity true the grille in m/s
- Ak = Effective area in m²
- Lw(A) = Acoustic power in dB(A)
|