Air exhaust ceiling diffusers with removable perforated plate
Explanation
PPRMB = Diffuser type
200 = Diffuser size (connection diameter)
Dimensions
|
160 | 300 | 160 | 200 | 400 | 200 | 250 | 500 | 250 |
Quick selection
|
Q | Ak | 0.0302 | 0.0591 | 0.0976 | 150 | Vk | 1.4 | 0.7 | | Ps | 18 | 4 | | Lw(A) | <20 | <20 | | 200 | Vk | 1.8 | 0.9 | 0.6 | Ps | 29 | 7 | 3 | Lw(A) | <20 | <20 | <20 | 250 | Vk | 2.3 | 1.2 | 0.7 | Ps | 47 | 13 | 4 | Lw(A) | 24 | <20 | <20 | 300 | Vk | 2.8 | 1.4 | 0.9 | Ps | 70 | 18 | 7 | Lw(A) | 30 | <20 | <20 | 400 | Vk | | 1.9 | 1.1 | Ps | | 32 | 11 | Lw(A) | | <20 | <20 | 500 | Vk | | 2.4 | 1.4 | Ps | | 52 | 18 | Lw(A) | | 27 | <20 | 600 | Vk | | 2.8 | 1.7 | Ps | | 70 | 26 | Lw(A) | | 33 | <20 | 800 | Vk | | | 2.3 | Ps | | | 47 | Lw(A) | | | 28 | 1000 | Vk | | | 2.8 | Ps | | | 70 | Lw(A) | | | 35 |
Symbols and specifications
- Q = Air Volume in m³/h
- Ak = Effective surface (free area) in m²
- Vk = Average effective velocity through the grill in m/s
- Ps = Static pressure loss given in Pa
- Lw(A) = Acoustic power in dB(A)
- The values are given for isothermal supply air
- For all special requirements, please contact our engineering office.
|