This site uses cookies and related technologies, as described in our privacy policy, for purposes that may include site operation, analytics, enhanced user experience, or advertising. You may choose to consent to our use of these technologies, or manage your own preferences.
Air exhaust ceiling diffusers with removable perforated plate
Brand
Cairox
Application
For air exhaust in ventilation and air conditioning systems
Material
Steel
Colour
Standard colour white, RAL 9016
Other colours available upon request
Composition
Perforated removable front plate with incorporated top entry plenum box
Perforated innerpart to be opened easily by push-push system
Text for tender
The square air exhaust ceiling diffusers have a perforated front plate and an incorporated plenum box. They are made of steel and finished in white powder coating RAL 9016.
Cairox type PPRMB
The square air exhaust ceiling diffusers have a perforated front plate and an incorporated plenum box. They are made of steel and finished in white powder coating RAL 9016.
Cairox type PPRMB
Order example
PPRMB, 200
Explanation
PPRMB = Diffuser type
200 = Diffuser size (connection diameter)
Artikelen
Artikelselectie-assistent
Type
Specificatie
Artikelnummer
Type
Specificatie
E-shop
I100114211101
MC FLR 225 4/0
600 x 400 x 400 mm
I100114111100
MC FLR 325/400 4/0
750 x 508,5 x 400 mm
I100114212100
MC FLR 325/400 2/2
750 x 543 x 400 mm
I100114211110
MC FLR 450/600 4/0
850 x 600 x 400 mm
Dimensions
PPRMB
A [mm]
ØN [mm]
160
300
160
200
400
200
250
500
250
Quick selection
PPRMB
300/160
400/200
500/250
Q
Ak
0.0302
0.0591
0.0976
150
Vk
1.4
0.7
Ps
18
4
Lw(A)
<20
<20
200
Vk
1.8
0.9
0.6
Ps
29
7
3
Lw(A)
<20
<20
<20
250
Vk
2.3
1.2
0.7
Ps
47
13
4
Lw(A)
24
<20
<20
300
Vk
2.8
1.4
0.9
Ps
70
18
7
Lw(A)
30
<20
<20
400
Vk
1.9
1.1
Ps
32
11
Lw(A)
<20
<20
500
Vk
2.4
1.4
Ps
52
18
Lw(A)
27
<20
600
Vk
2.8
1.7
Ps
70
26
Lw(A)
33
<20
800
Vk
2.3
Ps
47
Lw(A)
28
1000
Vk
2.8
Ps
70
Lw(A)
35
Symbols and specifications
Q = Air Volume in m³/h
Ak = Effective surface (free area) in m²
Vk = Average effective velocity through the grill in m/s
Ps = Static pressure loss given in Pa
Lw(A) = Acoustic power in dB(A)
The values are given for isothermal supply air