Constant volume control dampers made of fire retardant plastics. The range covers an air flow range between 15 up to 700 m³/h within a pressure range from 50 up to 250 Pa. Air flow can easily be adjusted within the airflow range of each damper.
Pressure loss
Symbols and specifications
- Q [m³/h] = Air flow rate in m³/h
- Q KVR-R = Set
flow rate in the volume control damper
- Ps [Pa] = Static
pressure loss in the volume control damper in Pa
- The graphs characterize the variations in the air flow in air supply and extraction with respect to the pressure differential in Pascal at a pressure set between 50 and 250Pa. The flow rates shown are average values and may vary as follows:
- For Ø80: +/- 3 m³/h
- For Ø100 and Ø125: +/- 3 m³/h for air volume <= 50 m³/h, +/-5% for air volume >50 m³/h
- For Ø150, Ø160, Ø200 and Ø250: +/- 5%
Construction
- 1. Collar with sealing
- 2. Intermediate piece according to the air flow rate
- 3. Casing
- 4. Regulating element
- 5. Air flow rate regulating module
- 6. Blocking screw for regulating module
Dimensions
|
Ø 80 | 76 | 76 | 55 | Ø 100 | 96 | 93 | 70 | Ø 125 | 120 | 117 | 86 | Ø 150 | 146 | 148 | 91 | Ø 160 | 146 | 148 | 91 | Ø 200 | 190 | 195 | 91 | Ø 250 | 245 | 236 | 127 |
Adjustment
Sound data
|
|
15 | 25 | 29 | 32 | 35 | 25 | 26 | 30 | 33 | 36 | 30 | 26 | 31 | 35 | 38 | 45 | 27 | 33 | 36 | 39 | 50 | 29 | 35 | 37 | 41 | 60 | 32 | 37 | 39 | 42 | 75 | 32 | 37 | 40 | 42 | 90 | 32 | 38 | 41 | 44 | 100 | 33 | 39 | 42 | 45 | 120 | 30 | 34 | 39 | 42 | 150 | 33 | 37 | 41 | 45 | 180 | 34 | 40 | 44 | 47 | 210 | 34 | 40 | 42 | 44 | 240 | 35 | 41 | 44 | 47 | 270 | 37 | 43 | 45 | 49 | 300 | 33 | 37 | 42 | 45 | 350 | 35 | 40 | 44 | 47 | 400 | 37 | 42 | 45 | 50 | 450 | 38 | 44 | 46 | 51 | 500 | 39 | 46 | 48 | 53 |
Symbols and specifications
- Q [m³/h] = Air flow rate in m³/h
- Ps [Pa] = Static pressure loss in the volume control damper in Pa
- Lw [dB(A)] = Sound power in dB(A)
|