The TRD 25 is a thermally and acoustically insulated duct type SONOFLEX 25
Application
The TRD 25 flexible ducts are used in ventilation, air conditioning, and air handling systems where high mechanical strength, temperature, fire-resistance, and thermal and sound attenuating qualities are required
Composition
Micro-perforated inner duct of the ALUFLEX type, consisting of 1 layer of 7 μ aluminium , and 2 layers of 12 μ polyester each (one aliminized), total thickness without glue: 31 μ
Metalized polyester outer jacket 3-layer laminate, consisting of 2 layers of polyester of 12 μ each and 1 aluminium of 7µ. Total thickness without glue: 45 μ
Fibreglass insulation:
Density: 16 kg/m³
Thickness: 25 mm
Thermal resistance: 0,65 K.m²/W
Thermal conductivity: 0,039 W/m-K
Colour: pink
Polyester barrier of 12µ between insulation and inner duct
Wire spacing: a steel spiral spring of different thicknesses and a pitch of 25mm (Ø82-90mm), 36mm (Ø102-406mm)
Colour: Aluminium
Both ends reinforced with alutape connection for easy mounting
Specification
Temperature range: From - 30°C till + 140°C
Air velocity (max): 20 m/s
Operating pressure: -188 up to 1500 Pa
Center bend radius: 1 x Diameter minimum
Fire resistance: Class B - s1, d0 according to EN 13501-1
As the product does not contain PVC, no toxic vapours are released should fire occur
Produced according EN 13180: Dia Class B, Thightness Class C, Sag<4°, Crushing strength 13-35kg compressed; 2.5kg uncompressed.
Chemical resistance
Good resistance to many organic solvents
Moderate resistance to acid and base
Static properties
The TRD 25 is suitable for applications where static discharges have to be avoided
Restrictions
The TRD 25 ducts are not suitable for transporting air with a high concentration of acid and base
The TRD 25 can not be used for discharging combustion gases from open fire places and oil-fired boilers
Accessories
Clamps, type MCA
Order example
TRD, 254, 1000
Explanation :
TRD = Type of Flexible duct
254 = Diameter of flexible duct
1000 = Length of flexible duct
Text for tender
The connection of the plenum boxes shall be done with the use of acoustically and thermally insulated flexible ducts, B - s1, d0 according to French standard. The outer jacket shall be reinforced to prevent rupture
Brand ATC Type TRD 25
The connection of the plenum boxes shall be done with the use of acoustically and thermally insulated flexible ducts, B - s1, d0 according to French standard. The outer jacket shall be reinforced to prevent rupture
Brand ATC Type TRD 25
Pressure loss graph
Sound attenuation for 1m duct - Tolerance +/- 2 dB
TRD
Test report Peutz bv - The Netherlands n° A3308-1-RA-001