CR2+BFLT/BFNT 24 • Motorized circular fire dampers EI120S

  • Fire dampers
  • Circular
  • EI120S
  • Motorized
  • EN1366-2
  • BELIMO 24V
  • Ø 355 - 630

Motorized circular fire dampers with a fire resistance of 120 minutes. When the temperature of the thermo-electric fuse in the damper rises above 72 °C the damper will close. When closed, the expanding material around the fireblade will assure a fire and air-tight seal against hot air and smoke. The tunnel is made out of galvanized steel. The CR2 + BFLT/BFNT 24 fire dampers have a motorized operating mechanism with indication of the blade position including begin of range or end switch.

Application

  • Fire compartimentation
  • To close and seal off ventilation ducts in case of fire
  • For air temperatures of -10°C up to temperature of the thermo-electric fuse
  • For air with RV 0-96%
  • Range of Ø355 up to Ø630 mm
  • For size Ø100 up to Ø315 see type CR120
  • To be mounted horizontally or vertically

Material

  • Galvanized steel

Construction

Composition

  • Galvanized steel tunnel
  • Fireproof blade in fibersilicate
  • Intumescent strip around the valve
  • 24V Actuator BELIMO BFLT 24 (small valves) of BFNT 24 (other sizes)

  • 1. Steel tunnel
  • 2. Damper blade
  • 3. Operating mechanism with:
    • manual rearmation option
    • blade position indicator
  • 4. Cold packing
  • 5. Blade bumper
  • 6. Intumescent strip
  • 7. Thermo-electric fuse
  • 8. Rubber sealing

Mounting

  • To be inserted in fire resistant walls or floors according to the mounting instructions delivered with the valves
  • To be connected with round air ducts
  • To be electrically wired to the fire detection or building installation

Certification

  • Classified EI120(ve,ho i<->o)S at 500Pa according EN 13501-3 in ridid wall and rigid floor
  • Classified EI60(ve i<->o)S at 500Pa, EI90(ve i<->o)S at 300Pa and EI120(ve i<->o)S at 500Pa according EN 13501-3 in different flexible wall types
  • Certified with test report Efectis 10-A-459 / EFR-19-005409 or WFRG 16128
  • Airtight EN 1751 class B, Class C upon request
  • CE marked

Accessories

  • Fire resistant plaster, type BP

Text for tender

Copy
  • The fire dampers shall be of the round type with a fire resistance of 120 Minutes, certified according to EN 13501-3. They will consist of a galvanized steel tunnel and fireproof valve. The control mechanism will be automatically operated by means of an actuator and shall have a blade position indicator and thermo-electrical fusible link of 72 °C
  • type CR2 + BFLT/BFNT 24

Order example

  • CR2 + BFLT 24, 315

Explanation

CR2 = Round fire damper 120 Minutes

BFLT 24 = Actuator 24V with thermostatic fuse

315 = Connection diameter

Quick selection

øDAkv12345678
2000.013Q113226339452566679792905
Vk2.404.907.309.7012.2014.6017.0219.40
Ps4.5017.804071111160218285
Lw(A)3040465053565860
2500.025Q177353530707884106012371414
Vk1.903.905.807.809.7011.7013.6015.50
Ps21021385986116152
Lw(A)2838444952555759
3150.047Q28156184211221403168319642244
Vk1.703.3056.608.309.9011.6013.20
Ps15122133476483
Lw(A)2737434750535557
3550.064Q356713106914251782213824942851
Vk1.503.104.606.207.709.3010.8012.40
Ps1491624354862
Lw(A)2636424750525557
4000.086Q452905135718102262271431673619
Vk1.502.904.405.907.308.8010.2011.70
Ps1371218263646
Lw(A)2536424649525456
4500.114Q5731145171822902863343540084580
Vk1.402.804.205.6078.409.8011.20
Ps125914202735
Lw(A)2535414548515355
5000.146Q7071414212128273534424149485655
Vk1.302.7045.406.708.109.4010.80
Ps024711162128
Lw(A)2434404548515355
5600.189Q8871773266035474433532062077093
Vk1.302.603.905.206.507.809.1010.40
Ps01358121622
Lw(A)2434404447505254
6300.247Q11222244336744895611673378558978
Vk1.302.503.8056.307.608.8010.10
Ps01247101418
Lw(A)2333394347495254

Symbols and specifications

  • Ak = Effective area in m²
  • v = Air velocity in the duct in m/s
  • Q = Air volume in m³/h
  • Vk = Effective velocity through the damper in m/s
  • Ps = Static pressure in Pa
  • Lw(A) = Acoustic power in dB(A)
  • Dia = Duct diameter in mm

Dimensions

P

Q

Z (H<300)

Z (H>=300)

x

y

CR2 + BFLT/BFNT 24

110

210

80

180

=(ØD/2)-265

=(ØD/2)-134

Electrical connection