PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

DVS-B+K • Fire resistant air exhaust valves EI60S

White fire resistant ventilation exhaust valves with thermal fuse of 70°C and fire resistance class EI60(veo->i)S

Application

  • For ventilation purposes and fire compartimentation in walls with fire resistance of 60 minutes

Material

  • Steel

Colour

  • White, RAL 9010

Construction

Composition

  1. Steel body with white powder coated finish
  2. Moulded fireproof heat-resistant material
  3. Disc in ceramic felt
  4. Threaded rod
  5. Central core in powder coated steel
  6. Standard mounting frame in galvanized steel
  7. Locking device
  8. Threaded support with fuse
  9. Fuse-hook
  10. Return spring in steel
  11. Fuse 70°C
  12. Locking clips

x: total length when locked (after exposure to heat)

Mounting

  • The valve should be mounted in a brick wall or partition gypsum plaster, according to the following methodology:
    • Make a reservation DN + 40 mm in the wall crossing. Ø particular case of a partition gypsum: spare a square booking dimension (DN 70) x (DN 70) therein a trimmer with a headband Promatect'H thickness 15mm.
    • Fix the pipe in DN standardized circular, to the mounting flange.
    • Position and the wedge together in the center of the book so that the folded edge of the flange comes into bare outer face of the receiving valve.
    • Grouting periphery coated with gypsum mixed with sand.
    • Adjusting the opening of the movable part of the valve (see graphs)
    • Install the valve set in the standby position, in its collar by rotating 1/4 turn: to build on the outer edge of the body: do not put stress on the central core!

Certification

  • CE Certified under the name BCF-2-EI60S
  • CE certified 1812-CPD-1039
  • Conforme according EN15650-2010
  • Classification EI60(veo->i)S
  • Service pressure 300Pa
  • Fuse tested according ISO 10294-4

Accessories

  • Mountingframe (included)
  • End of range switch, type FDC DVS-B+K

Text for tender

Copy
  • The ventilation valves will be fire resistant EI60(veo->i)S with thermal fuse of 70° and equipped with mountingframe.
  • Finished white, RAL 9010
  • type DVS-B+K

Order example

  • DVS-B + K, 125

Explanation

DVS-B+K = Type of fire resistant valve

125 = Connection diameter

Quick selection

QDVS-B+K100125
s3691236912
30Ps4012      
Lw(A)3225      
40Ps7525  45   
Lw(A)4025  27   
60Ps 5018 10030  
Lw(A) 4435 4025  
80Ps  3218 51  
Lw(A)  4336 34  
100Ps  5028 8035 
Lw(A)  5042 4232 
120Ps   40  5124
Lw(A)   48  3932
140Ps      7030
Lw(A)      4836
180Ps       50
Lw(A)       45

Selection graphs

Symbols and specifications

  • Q = Air volume in m³/h
  • Ps = Static pressure in Pa
  • s = Distance between the central cone and the body of the valve in mm
  • Lw(A) = Acoustic power in dB(A)
  • 100, 125 = Duct connection in mm

Dimensions

DVS-B+K

ØA [mm]

B [mm]

C [mm]

x [mm]

ØDN [mm]

100

154

37

35

150

99

125

182

3735

150

124