ETAMASTER 150L EC 01 + ESCP010
ETAMASTER = type of fan
150L = diameter (large housing)
EC = EC-motor
01 = type
ESCP010 = potentiometer
Air performance data
|
|
ETAMASTER 160L EC 01 | 762 | 708 | 650 | 593 | 529 | 204 | - | - | - | - | - | - | ETAMASTER 200 EC 01 | 1218 | 1118 | 1013 | 907 | 766 | 383 | 125 | - | - | - | - | - | ETAMASTER 250 EC K 01 | 1800 | 1700 | 1600 | 1475 | 1350 | 1230 | 1075 | 500 | - | - | - | - | ETAMASTER 250 EC 02 | 2112 | 2044 | 1971 | 1896 | 1818 | 1735 | 1557 | 1325 | 441 | 288 | - | - | ETAMASTER 280 EC 01 | 2353 | 2245 | 2131 | 2019 | 1902 | 1775 | 1465 | 545 | 230 | - | - | - | ETAMASTER 315 EC 01 | 2805 | 2634 | 2462 | 2277 | 2071 | 1885 | 1179 | 524 | - | - | - | - | ETAMASTER 355 EC 01 | 3082 | 2817 | 2544 | 2263 | 2014 | 1639 | 499 | - | - | - | - | - | ETAMASTER 355 EC 02 | 4662 | 4520 | 4367 | 4207 | 4049 | 3887 | 3546 | 3178 | 2662 | 1130 | 857 | 383 | ETAMASTER 400 EC 01 | 5532 | 5342 | 5135 | 4935 | 4722 | 4494 | 3951 | 3459 | 2257 | 1220 | 661 | - |
Selection curves
Selection curves
Technical data
|
|
ETAMASTER 160L EC 01 | 1 x 230 | 73 | 0.7 | ESCP010 | 52.8 | 45 | 45 | -30 | 3730 | 73 | 76 | 56 | ETAMASTER 200 EC 01 | 1 x 230 | 121 | 1 | ESCP010 | 48 | 45 | 45 | -30 | 3170 | 76 | 79 | 62 | ETAMASTER 200 EC K 01 | 1 x 230 | 179 | 1.5 | ESCP010 | 63.9 | 45 | 45 | -30 | 3110 | 78 | 80 | 67 | ETAMASTER 250 EC K 01 | 1 x 230 | 189 | 1.42 | ESCP010 | 66.9 | 50 | 50 | -30 | 3279 | 76 | 79 | 62 | ETAMASTER 250 EC 02 | 1 x 230 | 304 | 2.1 | ESCP010 | 62.3 | 45 | 45 | -30 | 3880 | 81 | 85 | 65 | ETAMASTER 315 EC 01 | 1 x 230 | 282 | 2 | ESCP010 | 56.7 | 45 | 45 | -30 | 2800 | 79 | 82 | 71 | ETAMASTER 355 EC 01 | 1 x 230 | 261 | 1.8 | ESCP010 | 56.5 | 35 | 35 | -25 | 2170 | 75 | 78 | 62 | ETAMASTER 355 EC 02 | 1 x 230 | 731 | 3.4 | ESCP010 | 62 | 60 | 60 | -25 | 3010 | 84 | 87 | 68 | ETAMASTER 400 EC 01 | 1 x 230 | 729 | 3.4 | ESCP010 | 65.3 | 60 | 60 | -25 | 2620 | 82 | 86 | 62 |
- SCP =
Potentiometer 0-10V
- ŋt =
Maximum total efficiency
- Tm = Maximum air temperature
- Tu = Maximum ambient temperature
- To = Minimum operating temperature
- Lwa 2 = Casing sound power level
- Lwa 5 =
Sound power level @inlet
- Lwa 6 =
Sound power level @outlet
- The sound power levels are measured according to DIN 45635 part 2 & 38
Dimensions
|
|
ETAMASTER 160L EC 01 | 137,7 | 210,1 | 159 | 238,5 | 289 | 2,6 | ETAMASTER 200 EC 01 | 163 | 252 | 199 | 280,2 | 325 | 3,2 | ETAMASTER 250 EC K 01 | 169,7 | 268 | 249 | 299,4 | 215 | 5,7 | ETAMASTER 250 EC 02 | 169,7 | 268 | 249 | 299,4 | 215 | 4,1 | ETAMASTER 315 EC 01 | 284 | 325,1 | 314 | 361,4 | 300 | 6,9 | ETAMASTER 355 EC 01 | 316 | 365 | 354 | 401 | 325 | 8,7 | ETAMASTER 355 EC 02 | 316 | 365 | 354 | 401 | 325 | 9,8 | ETAMASTER 400 EC 01 | 350 | 410 | 399 | 452 | 350 | 11,7 |
|