PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

CVI-DP • Fan boxes - 25 mm insulation and safety switch

Insulated direct driven centrifugal fan box

Application

  • Air supply or exhaust of offices, restaurants or shops
  • Convenient for indoor and outdoor installation

Composition

  • The casing of the CVI-DP is made of double-walled galvanized steel sheets with 25 mm insulation (fire class A1 according to EN 13501-1)
  • Two removable side panels allow quick and easy maintenance
  • Round connections on suction and discharge side
  • Equipped with a work switch
  • A connection box for electrical connection is provided

Fan

  • Low pressure centrifugal fan with forward curved impeller manufactured from pressed and formed galvanised sheet steel
  • All impellers are factory fitted to the motors and dynamically balanced to minimise vibration

Motor

  • Protection class IP55 of IP 44, insulation class F
  • Supply: 230Vac 1ph or 230/400Vac 3ph
  • All models include a Safety Thermal Overload protection device

Accessories

  • Auto transformer 230V, type TSC-1
  • Auto transformer 3x400V, type TSCTK-4
  • Frequency converter 230V in / 3x230V out, type FIS(-C)-13-B
  • Frequency converter 3x400V in / 3x400V out, type FIS(-C)-44-B
  • Clamping strip, type BMK

Air performance data

 Q [m³/h]
50 Pa100 Pa150 Pa200 Pa250 Pa300 Pa350 Pa400 Pa450 Pa500 Pa550 Pa600 Pa650 Pa700 Pa750 Pa
CVI-DP 7/7-4A M-170016501450750----------
CVI-DP 9/9-6 M280026002100--- --------
CVI-DP 9/9-4 M--35303375315028002525700-------
CVI-DP 10/10-6 M-335031752750350----------
CVI-DP 12/9-6 M---468041503500860--------
CVI-DP 12/12-6 M----48502000685--------
CVI-DP 12/12-6 T---6550575046801450935-------
CVI-DP 15/15-6 T------9000662550001310435- --

Selection curves

Note

The CVI-DP fan may never be used with free inlet. There should be a minimal counter-pressure as indicated above. Please measure the current at first starting.

Technical data

 U [V]P [W]I [A]SCTu [°C]IPn [rpm]Lp, max [dB(A)]
CVI-DP 7/7-4A M1 x 2301471.6TSC-1-224055142059
CVI-DP 9/9-6 M1 x 2302452.2TSC-1-40405596078
CVI-DP 9/9-4 M1 x 2305504.6TSC-1-504055142067
CVI-DP 10/10-6 M1 x 2302452.8TSC-1-40404498064
CVI-DP 12/9-6 M1 x 2307505.5TSC-1-70405591379
CVI-DP 12/12-6 M1 x 23010006.3TSC-1-70404489981
CVI-DP 12/12-6 T3 x 230/40011005.2 - 3FIS-1320E-1.5-B / TSCTK-4-30404498074
CVI-DP 15/15-6 T3 x 230/40022008.82 - 5.1FIS-1320E-2.2-B / FIS-4420E-2.2-B405599086

  • SC = Speed controller
  • Tu = Maximum ambient temperature
  • Lpa = Sound pressure level

Dimensions

 A [mm]B [mm]C [mm]D [mm]E1 [mm]E2 [mm]F [mm]G [mm][kg]
CVI-DP 7/74504504502501481482041028
CVI-DP 9/95505505503551401402051035
CVI-DP 10/106006006004001541542056039
CVI-DP 12/96506507004501551552066048
CVI-DP 12/126506507004501551552066055
CVI-DP 15/158008009505601952752091092
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be