Direct driven centrifugal fan box
Air performance data
|
|
CVI-SP 7/7-4A M | - | 1700 | 1650 | 1450 | 750 | - | - | - | CVI-SP 9/9-6 M | 2800 | 2600 | 2100 | - | - | - | - | - | CVI-SP 9/9-4 M | - | - | 3530 | 3375 | 3150 | 2800 | 2525 | 700 | CVI-SP 10/10-6 M | - | 3350 | 3175 | 2750 | 350 | - | - | - | CVI-SP 12/9-6 M | - | - | - | 4680 | 4150 | 3500 | 860 | - | CVI-SP 12/12-6 M | - | - | - | - | 4850 | 2000 | 685 | - | CVI-SP 12/12-6 T | - | - | - | 6550 | 5750 | 4680 | 1450 | 935 |
Selection curves
Selection curves
Note
The CVI-SP fan may never be used with free inlet. There should be a minimal
counter-pressure as indicated above. Please measure the current at first
starting.
Technical data
|
CVI-SP 7/7-4A M | 1 x 230 | 147 | 1.6 | TSC-1-22 | 40 | 55 | 1420 | 60 | CVI-SP 9/9-6 M | 1 x 230 | 245 | 2.2 | TSC-1-40 | 40 | 55 | 960 | 62 | CVI-SP 9/9-4 M | 1 x 230 | 550 | 4.6 | TSC-1-50 | 40 | 55 | 1420 | 66 | CVI-SP 10/10-6 M | 1 x 230 | 245 | 2.8 | TSC-1-40 | 40 | 44 | 980 | 64 | CVI-SP 12/9-6 M | 1 x 230 | 750 | 5.5 | TSC-1-70 | 40 | 55 | 913 | 67 | CVI-SP 12/12-6 M | 1 x 230 | 1000 | 6.3 | TSC-1-70 | 40 | 44 | 899 | 67 | CVI-SP 12/12-6 T | 3 x 230/400 | 1100 | 5.2 / 3.0 | FIS(-C)-13-B / FIS(-C)-44-B / TSCTK-4-40 | 40 | 44 | 980 | 68 |
- SC = Speed controller
- Tu = Maximum ambient temperature
- Lpa = Sound pressure level
Dimensions
|
CVI-SP 7/7
| 450
| 450
| 450
| 250
| 148
| 20 | 410 | 25
| CVI-SP 9/9
| 550
| 550
| 550
| 355
| 140
| 20 | 510 | 35
| CVI-SP 10/10
| 600
| 600
| 600
| 400
| 154
| 20 | 560 | 39
| CVI-SP 12/9
| 650
| 650
| 700
| 450
| 155
| 20 | 660 | 53
| CVI-SP 12/12
| 650
| 650
| 700
| 450
| 155
| 20 | 660 | 55
|
|