This site uses cookies and related technologies, as described in our privacy policy, for purposes that may include site operation, analytics, enhanced user experience, or advertising. You may choose to consent to our use of these technologies, or manage your own preferences.
Flat heat recovery unit with counterflow heat exchanger, either without battery or with integrated post-heating battery (electric or water), for indoor installation. The unit is suitable for mounting in a false ceiling, on the floor or against the wall. The units are available with a flow rate up to approx. 3.500 m³/h and have rectangular connections.
The unit is EPB-tested according to NBN EN 308.
Brand
R-COVERY by SALDA
Application
Ventilation for residential and non residential applications
For indoor installation (ceiling model; floor or wall mounting possible with optional accessories)
Specifications
Outer panel in galvanised steel
RAL7040 (Grey) (corrosion class C3)
Inner panel in galvanised steel
(corrosion class C2)
50
mm insulation
Mineral
wool insulation, fire class A1
Rectangular
connections
Motorised registers and flexible
sleeves (OPTIONAL)
Built-in heating battery available (electric or water)
Automatic
bypass On/Off
Standard
Modbus communication
MB-GATEWAY communication possible
with Modbus/BACnet/TCP-IP (Webserver or App)
Standard
constant flow control
Optional constant pressure, CO2 or humidity control (sensors not included)
Filter
detection via pressure switch
Control
not included
Fan
Direct driven EC DC fan with backward curved impeller
Constant flow control
Exchanger
High efficiency counterflow heat exchanger in aluminium> 79%
With condensate tray in stainless steel
Filter
The AmberAir Compact CXP is equipped with panel filters M5 - ISO 16890 ePM10 55% (extraction) / F7 - ISO 16890 ePM1 70% (supply)
Versions
AmberAir
Compact CXP-xL NB MCB: Size x, left-hand version, without battery, MCB control
AmberAir
Compact CXP-xL BE MCB: Size x, left-hand version, with electric battery, MCB
control
AmberAir
Compact CXP-xL BC MCB: Size x, left-hand version, with hot water battery, MCB
control
AmberAir
Compact CXP-xR NB MCB: Size x, right-hand version, without battery, MCB control
AmberAir
Compact CXP-xR BE MCB: Size x, right-hand version, with electric battery, MCB
control
AmberAir
Compact CXP xR-BC MCB: Size x, right-hand version, with hot water battery, MCB
control
Certification
Tested according to NBN EN 308: www.epbd.be
Tested according to EUROVENT classifications according to EN13053
Mechanical strength: D1
Air tightness class: L1
Thermal transfer class: T3
Thermal bridge factor: TB2
Filter leakage: F9
Mounting
The device is delivered in 1 part
Accessories
Wall control with touch screen, type TS-AIR
Airtight regulation valve, type RM-RBS
Connection sleeve, type MTS-R
Replacement filter, type FS-CXP
Connection of multiple 0-10V sensors, type MM6-24/D
Order example
AmberAir Compact CXP-4L BE MCB
Explanation
CXP = with counterflow heat exchanger
4 = construction size
L = left-hand version
BE = electric post-heating
MCB = type of regulation
Articles
Artikelselectie-assistent
Type
Artikelnummer
Type
E-shop
J120525001000
SRFA
J120525001001
SRFA-R
J120525001005
SRFA-5
J120525001020
SRFA-S2
J120525001021
SRFA-S2-R
J120525001025
SRFA-S2-5
Selection curves
EPB values
Q [m³/h]
ŋ t,epb [%]
Pelec,epb [W]
AmberAir Compact CXP-4
2992
79
1729
Q = Flow rate
ŋ t,epb = Thermal efficiency EPB
Pelec,epb = Total electric power EPB
Technical data
AmberAir Compact CXP-1
CXP-1 NB
CXP-1 BE
CXP-1 BC
Main power supply
[50Hz/VAC]
1 x 230
1 x 230
1 x 230
Heating battery
Electric power
[kW]
-
3,6
-
EC Fans
Power supply
[50Hz/VAC]
1 x 230
1 x 230
1 x 230
Extraction fan
Power/current
[kW/A]
0,38/2,50
0,38/2,50
0,38/2,50
Extraction fan
Fan speed
[rpm]
3370
3370
3370
Supply fan
Power/current
[kW/A]
0,38/2,50
0,38/2,50
0,38/2,50
Supply fan
Fan speed
[rpm]
3370
3370
3370
Max. absorbed power/current
[kW/A]
0,813/5,22
4,41/20,90
0,813/5,22
Automatic defrost
integrated
integrated
integrated
Thermal insulation
[mm]
50
50
50
AmberAir Compact CXP-2
CXP-2 NB
CXP-2 BE
CXP-2 BC
Main power supply
[50Hz/VAC]
1 x 230
3 x 400
1 x 230
Heating battery
Electric power
[kW]
-
6,0
-
EC Fans
Power supply
[50Hz/VAC]
1 x 230
1 x 230
1 x 230
Extraction fan
Power/current
[kW/A]
0,76/3,80
0,76/3,80
0,76/3,80
Extraction fan
Fan speed
[rpm]
3530
3530
3530
Supply fan
Power/current
[kW/A]
0,76/3,80
0.76/3.80
0.76/3.80
Supply fan
Fan speed
[rpm]
3530
3530
3530
Max. absorbed power/current
[kW/A]
1,61/8,00
6,85/16,70
1,61/8,00
Automatic defrost
integrated
integrated
integrated
Thermal insulation
[mm]
50
50
50
AmberAir Compact CXP-3
CXP-3 NB
CXP-3 BE
CXP-3 BC
Main power supply
[50Hz/VAC]
3 x 400
3 x 400
3 x 400
Heating battery
Electric power
[kW]
-
9,0
-
EC Fans
Power supply
[50Hz/VAC]
3 x 400
3 x 400
3 x 400
Extraction fan
Power/current
[kW/A]
1,05/1,60
1,05/1,60
1,05/1,60
Extraction fan
Fan speed
[rpm]
3400
3400
3400
Supply fan
Power/current
[kW/A]
1,05/1,60
1,05/1,60
1,05/1,60
Supply fan
Fan speed
[rpm]
3400
3400
3400
Max. absorbed power/current
[kW/A]
2,15/3,42
11,20/16,40
2,15/3,42
Automatic defrost
integrated
integrated
integrated
Thermal insulation
[mm]
50
50
50
AmberAir Compact CXP-4
CXP-4 NB
CXP-4 BE
CXP-4 BC
Main power supply
[50Hz/VAC]
3 x 400
3 x 400
3 x 400
Heating battery
Electric power
[kW]
-
12,0
-
EC Fans
Power supply
[50Hz/VAC]
3 x 400
3 x 400
3 x 400
Extraction fan
Power/current
[kW/A]
1,80/2,80
1,80/2,80
1,80/2,80
Extraction fan
Fan speed
[rpm]
3410
3410
3410
Supply fan
Power/current
[kW/A]
1,80/2,80
1,80/2,80
1,80/2,80
Supply fan
Fan speed
[rpm]
3410
3410
3410
Max. absorbed power/current
[kW/A]
3,65/5,82
9,45/14,50
3,65/5,82
Automatic defrost
integrated
integrated
integrated
Thermal insulation
[mm]
50
50
50
Detailed technical data available on request
Note