AmberAir Compact CXV (Eurovent certified) is an air handling unit, perfectly suitable for installations in small spaces due to the modular concept and the air connections on the upper side. Air flow range up to 8.000 m³/h.
Application
Ventilation and air handling for commercial and industrial applications
School buildings, offices, retail stores, hotels and industry
Suitable for inside and outside installation
Composition
Joints-profile connected with blocking screws which ensures air tightness
Thermal breaking profiles with 25 mm plastic strips
Profiles internally rounded for easy cleaning
Galvanized steel and powder coated grey color RAL 7040
New generation polyurethane panels 45 mm
Internal adhesive gasket insulation
External gasket insulation
Extremely rigid plastic corners
Special plastic panels covering
Specifications
100% motorized bypass damper
Stainless steel drip tray – high draining efficiency 95%
Temperature range from -40°C up t +40°C
Demand control level with an integrated humidity sensor
Double-skinned casing panels
Polyurethane panels 45 mm
Galvanized steel powder coated corrosion class C3
Fan
High efficiency EC fans
Exchanger
Counterflow heat exchanger with high efficiency (up to 90%) in aluminium
Integrated modulating control electric heater (signal 0-10V) or integrated water heater
Filter
Panel filters F7 - ISO 16890 ePM1 70% and M5 - ISO 16890 ePM10 55% (pocket filters and other filter classes available upon request)
Regulation & functions
Integrated, intelligent regulation (plug & play)
Certification
Eurovent certified air handling units
Casing strength class: D1(M)
Casing air leakage class at 400 Pa & 700 Pa: L1(M)
Filter bypass leakage class: F9(M)
Thermal transmittance class: T2
Thermal bridging factor class: TB1
Selection curves
Selection curves
Technical data
1-CXV
2-CXV
3-CXV
4-CXV
5-CXV
6-CXV
7-CXV
Max. electric power input of fans
[kW]
0.76
0.94
1.43
2.56
3.8
4.55
5.68
Phase/voltage/frequency of fan
[f/VAC/Hz]
1~/230/50
1~/230/50
1~/230/50
1~/280/50
3~/400/50
3~/400/50
3~/400/50
Electric power input of electrical heater
[kW]
2
3
4
6
7
9
12
Phase/voltage/frequency of electrical heater
[f/VAC/Hz]
1~/230/50
1~/230/50
3~/400/50
3~/400/50
3~/400/50
3~/400/50
3~/400/50
Max. power consumption
Electrical heater
[kWh]
2.76
3.94
5.03
8.56
11
13.55
17.68
Water heater
1.16
1.44
2.03
3.26
4.6
5.45
6.68
Higher power input values of electrical heater or other type of fan available on demand