Heat
recovery unit with high efficiency up to 85% for ceiling mounting or semi-recessed
installation in the ceiling. The range includes 4 sizes and for flow rates from 150 to
1.100 m³/h.
Every
Eversky model comes standard with a built-in C02 regulation.
The Eversky unit is available in 4 versions:
- EVERSKY
FIRST (Basic unit with 2 filters, 2 fans and counterflow)
- EVERSKY
SMART (First with electric preheating battery)
- EVERSKY
PREMIUM (First with electric OR water post heating battery)
- EVERSKY
INFINITE (Premium with electric preheating battery)
The Eversky is a self-regulating unit with an extensive regulation module.
This unit
is only intended for an indoor installation.
The Eversky is the only school unit with a EUROVENT certificate!
EVERSKY 500 PRE BE D
Explanation
EVERSKY = type of heat recovery unit
500 = size (500-750-900-1100)
First = First uitvoering
Smart = Smart uitvoering
PRE = Premium version
INF = Infinite version
BE = with electric battery
D = DIVA EC regulation
Selection curves
Selection curves
Selection curves
Selection curves
- Q [m³/h] = Flow rate
- Pst [Pa] = Static pressure
- Pbat [Pa] = Pressure loss batteries
- BE = Electrical battery
- BC = Ho twater battery
- Pab [W] = Absorbed power per fan
- η [%] - EN 308 (20°C / 50%) = Efficiency
- Lwa pu = Sound power level in duct motor side
- Lwa ex = Sound power level in duct filter side
- Lpa @ 4m = Sound pressure level in free field with mounted inlet and outlet flanges
Technical data
|
|
500 | 2 x 169 | -25 / 60 | IP54/B | PTI | 230/1/50 | 2.7 | 230/1/50 | 7 | 230/1/50 | 11.4 | 750 | 2 x 170 | -25 / 60 | IP54/B | PTI | 230/1/50 | 2.8 | 230/1/50 | 8.2 | 230/1/50 | 13.7 | 900 | 4 x 169 | -25 / 60 | IP54/B | PTI | 230/1/50 | 5.3 | 230/1/50 | 10.8 | 230/1/50 | 16.3 | 1100 | 4 x 170 | -25 / 60 | IP54/B | PTI | 230/1/50 | 5.5 | 230/1/50 | 11 | 230/1/50 | 16.5 |
Battery
|
|
|
|
|
|
Capacity | [kW] | - | 1 | 1 | 1 + 1 | Temperature at air outtake of unit | [C°] | 16.2 | 16.3 | 16.3 | 14.6 | 22.2 | 22.3 | 19.6 | 22.3 | 20.6 | |
|
|
|
|
Capacity | [kW] | - | 1.25 | 1.25 | 1.25 + 1.25 | Temperature at air outtake of unit | [C°] | 16.5 | 16.7 | 16.7 | 13.6 | 21.5 | 21.7 | 19.6 | 21.7 | 18.6 | |
|
|
|
|
Capacity | [kW] | - | 1.25 | 1.25 | 1.25 + 1.25 | Temperature at air outtake of unit | [C°] | 16.3 | 16.5 | 16.6 | 12.8 | 20.5 | 20.7 | 17.7 | 20.8 | 17.0 | |
|
|
|
|
Capacity | [kW] | - | 1.25 | 1.25 | 1.25 + 1.25 | Temperature at air outtake of unit | [C°] | 16.4 | 16.6 | 16.8 | 14.9 | 19.8 | 20.0 | 17.1 | 20.2 | 18.4 |
Horizontal configurations - side by side flow - top view
The Eversky is only available in a right execution, viewed from the top of the device, following the direction of the airflow. This unit is supplied as standard with the possibility to easily change rear connections to side or top connections on site!
Dimensions
|
500 | 250 | 1670 | 490 | 645 | 815 | 445 | 1297 | 185 | 230 | 742 | 384 | 332 | 170 | 130 | 70 | 132 | 750 | 315 | 1985 | 555 | 830 | 900 | 510 | 1547 | 220 | 260 | 927 | 449 | 415 | 170 | 170 | 70 | 170 | 900 | 315 | 1985 | 555 | 830 | 900 | 510 | 1547 | 220 | 260 | 927 | 449 | 415 | 170 | 170 | 70 | 180 | 1100 | 315 | 2365 | 615 | 1085 | 1050 | 530 | 1924 | 220 | 280 | 1185 | 510 | 565 | 170 | 190 | 70 | 220 |
|