PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

CHR PRO • Heat recovery units system D ≤ 600 m3/h

Heat recovery unit system D with high efficiency for projects < 600 m3/h. Price available on request.

Brand

  • R-COVERY

Application

  • For projects
  • Ventilation with heat recovery for domestic and non-residential applications where high efficiency is required
  • Applicable for flow rates up to 600 m3/h
  • Available in different configurations
  • Suitable for indoor installation in a frost-free area

Specifications

  • Modulating electric preheater, 0 to 100%, with air guides
  • 'Bypass boost' function
  • Fireplace function
  • Vibration-free mounting
  • Supply voltage: 230Vac
  • Devices can be connected in cascade (up to 10 pieces) via eBus
  • ModBus communication
  • Filter wizard for end user

Composition

  • EC motors with constant flow (EBM) equipped with integrated anemometer
  • TFT touchscreen with integrated 4-position controller and wizard for maintenance and delivery
  • Supplied ball siphon with 32 mm connection
  • Automatic bypass valve (100%) with actuator, equipped with air guides and EPDM sealing
  • Housing made of epoxy-coated steel sheet (RAL 9016)
  • Inner part made of EPS foam parts without thermal bridges
  • Round connections of diameter 160mm
  • Standard 2x ISO coarse 60% filters
  • Easy maintenance: all components are removable from the front of the device

Fan

  • Energy-saving EC direct current EBM motors
  • Constant flow regulation
  • Integrated anemometer for fast and accurate measurement, even at low flow rates
  • Integrated into an energy efficient volute

Exchanger

  • Brand: Holmak TST35
  • Made from PETG
  • Large surface area for higher efficiency, reduced resistance and less noise
  • Equipped with guides with EPDM seal

Controller

  • eBus
  • ModBus
  • RJ12
  • USB for RF-FLR dongle
  • 24Vdc OUT signal

Certification

 NBN EN308EN13141-7
 Flow rateCapacity/motorht,epbSfp
 max. m³/hmax. Wmin. %W(m³/h)
CHR 225 PRO22542W850,17
CHR 325 PRO32259W860,15
CHR 400 PRO40177W850,17
CHR 600 PRO594143W840,25

Accessories

  • 4-position switch with filter indication, type CVREN 4
  • Wired touch-control with weekly timer, type TC E-BUS
  • Wireless remote controls en sensors, type FLR-RF
  • Humidity sensor (ducted sensor), type HRT REN
  • Wired CO2 sensors (up to 4 pieces) via eBus connection, type CO2 REN E-BUS
  • Bi-zonal demand ventilation based on time or CO2, type DCV
  • Replacement filters, type FS FLR
  • Mounting frame, type MC FLR
  • Additional external pre- or post-heating battery, type CVR-VNF

Order example

CHR 325 PRO R
Explanation
CHR = Cairox Heat Recovery unit, type of heat recovery unit
325 = maximum air flow in m³/h
PRO = for projects
R = right configuration (L = left configuration)

Technical data

  CHR 225 PROCHR 325 PROCHR 400 PROCHR 600 PRO
Supply voltage[V/Hz]230V/50Hz   
Dimensions (W x H x D)[mm]600 x 650 x 650750 x 650 x 560750 x 650 x 560800 x 850 x 661
Duct diameter[mm]4 x 1254 x 1604 x 1804 x 200
Ø connections of condensate drain[mm]32   
Weight[kg]29373749
Filter as standard (ISO16890) ISO COARSE 60% (G4)

Technical data

CHR 225 PRO
Q [m³/h]4050100150225
Ps [Pa]3651020404489100200
P [W]7.98.288.513.215.926.23461.582
[A]0.10.110.10.10.130.150.220.290.480.63
CHR 325 PRO
[m³/h]50100150250325
[Pa]25919214359118100200
[W]6.16.48.29.715.419.446.961.487.2116.5
[A]0.080.080.090.110.160.190.420.530.730.94
CHR 400 PRO
[m³/h]50100200300400
[Pa]23613255056113100200
[W]4.44.65.36.422.728.562.678.9126.6160.8
[A]0.060.060.070.080.250.310.580.711.011.26
CHR 600 PRO
[m³/h]100150300500600
[Pa]36613255069139100188
[W]12.112.517.218.344.554.2166.6203.1250288
[A]0.180.190.230.240.460.551.451.712.112.3

Sound data

CHR 225 PRO
Q [m³/h]50100100150150225225 
Ps [Pa]25255050100100150 
Lwa 2 [dB(A)]283133.538.540.545.547 
Lwa 5 [dB(A)]<30<34,5<36,5444347.548.5 
Lwa 6 [dB(A)]43.548.550.55557.562.564.5 
CHR 325 PRO
Q [m³/h]100150150200200250250325
Ps [Pa]25255050100100150150
Lwa 2 [dB(A)]2734354041464651
Lwa 5 [dB(A)]3240384644494955
Lwa 6 [dB(A)]4449515557616269
CHR 400 PRO
Q [m³/h]150250350400    
Ps [Pa]2550100100    
Lwa 2 [dB(A)]3743.55255    
Lwa 5 [dB(A)]43.546.55161    
Lwa 6 [dB(A)]505869.571    
CHR 600 PRO
Q [m³/h]150300300500500600600 
Ps [Pa]2550100100150100150 
Lwa 2 [dB(A)]37.545.5465654.556.556.5 
Lwa 5 [dB(A)]354542.5515253.556.5 
Lwa 6 [dB(A)]43.55353.560.561.56266.6 

I1 = Power consumption, excluding preheater
I2 = Power consumption, including preheater

  • Lwa 2 = Ambient sound power
  • Lwa 5 = Sound power on the suction side
  • Lwa 6 = Sound power on the discharge side

HELPCopyrightSales conditionsCookie policyfujitsu-airco.be