The HRC70 80 is an air/water heat pump that is suitable for heating water at high temperatures. The monoblock unit is filled with the natural refrigerant propane (R290) and easily reaches water temperatures of up to 70°C. The device guarantees proper operation at outside temperatures down to -20°C.
The HRC70 80 is a heating only unit that uses 2 scroll compressors of equal capacity, which are equipped with soft starters as standard. This ensures 2 power stages and low power consumption. Due to the specific construction, the device will switch to defrost mode less often and the defrost cycle will be completed as efficiently as possible.
The unit maintains its high COP values even at negative outside temperatures. Possibility to cascade 2 HRC70 80 devices for a total power of 180 kW.
Brand
Auer - Intuis
Application
Production of domestic hot water
Floor heating
Fan coils
Radiators
Also available in a cascade of 2 heat pumps HRC70 80 on 1 Pilote
Z2
Composition
Monoblock heat pump (outdoor unit) HRC70 80 kW with :
10 m long bus cable for communication between the HRC70 80 and the Pilote Z2 (3 core and already connected to HRC70 80 ) (do not place in parallel with power
cable).
Flexible pipes (Durite) of 5 m long and rigid insulated pipe to
indoor module (diameter according to distance between the two, see table at the
bottom of this page).
Filter 1"1/4 already installed in the return duct of the heat pump.
Primary pump already installed in the heat pump.
2,5 bar pressure relief valve mounted in the heat pump.
Indoor module Pilote Z2:
Buffertank/hydraulic decoupling bottle 200L with air vent, release valve and safety valve
4 x 2"1/2 flanges and 4 x 1"1/2" sleeves
Pressure sensor
Flow meter
Separate box with electronic regulation
USB stick (comes with manual)
Shut-off valve 1 "1/4
Filter tap 1 "1/4
Outdoor sensor for weather dependent control
Installation
The addition of an anti-corrosion agent or a glycol/anti-corrosion mixture is mandatory.
Accessories
Room thermostat RAM 812
Room sensor with display TH HRC70
DHW sensor DHW S HRC70
HRC70 Communication 20
HRC70 Communication 50
HRC PK CASCADE 6P10
Startup is chargeable (MANDATORY), type XSTARTUPJ, quotation available on request
Applicable boiler
Domestic hot water heater 300 liters, type SANI+ 300 R-AQUA
Domestic hot water heater 500 liters, type SANI+ 500 R-AQUA
Artikelen
Article selection assistant
Type
Length [mm]
Width [mm]
Height [mm]
Max. load [kg]
Packing [pieces]
Article number
Type
Length [mm]
Width [mm]
Height [mm]
Max. load [kg]
Packing [pieces]
E-shop
J050105100002
MPR 1000 (SET)
1000
130
95
700
2 pcs
=> Stock product central warehouse, except sales
=> Stock product local warehouses, except sales
=> Article with a volume discount
Notes
1. Painted welded tank 200 L
2. Hydraulic pressure sensor
3. Automatic purge
4. 6 bar safety valve
5. 2"1/2 valve
6. Thermowell
7. Support foot
8. Drain valve 1"1/4
9. Upper flange
10. Lower flange
11. Insulated finishing cover
Technical data
Technical specifications
HRC70 80 Z2 HEAT
Maximum water temperature
°C
70
Maximum heating capacity
kW
83
Heating capacity +7°C/+35°C
kW
76
COP +7°C/+35°C
4,20
Heating capacity +7°C/+45°C
kW
74,5
Heating capacity +7°C/+55°C
kW
73
Heating capacity -7°C/+35°C
kW
54
Heating capacity -7°C/+45°C
kW
53
Heating capacity -7°C/+65°C
kW
51
Energy class 35C°/55C°
A++
Annual energy consumption
kWh/year
28089
Operating range
°C
-20°C ~ +40°C
Outdoor unit dimensions HxWxD
mm
1580 x 2700 x 1200
Weight
kg
645
Air flow rate
m³/h
12000 to 24000
Rated water flow rate
m³/h
11
Condensate drain connection
G F
1"
Hydraulic connection diameter
Victualic/Rainuré
40/49 male
Sound level @ 5 m
dB(A)
39,5
Refrigerant (GWP)
R290 (3)
Amount of refrigerant R290
kg
4,5 (0,877)
Power supply
3 x 400V + N
Fuse
A
63 (D)
Cable section
A
5G16
Maximum absorbed power
A
62,2 A
Maximum starting current
A
115
Power position OFF (POFF)
kW
0,008
Power thermostat OFF (PTO)
kW
0,008
Power standby (PSB)
kW
0,008
Power carter heating (PCK)
kW
0,013
Technical data
Indoor module PILOTE
Z2
Power supply Pilote Z2
230V 1 ph
Minimum power cable width
mm²
3G1,5
Circuit breaker
A
10
Multifunctional tank
L
200
Dimensions (LxHxD) Pilote Z2 without the pumps
mm
775 x 1422 x 610
Dimensions (LxHxD) Regulation
mm
455 x 629 x 171
Weight Pilote Z2 without water
kg
81
Weight regulation
kg
9
Hydraulic connections
inch
Flange 2"1/2 Sleeves 1"1/2
Maximum pressure
bar
6
Dimensions
Minimum required piping diameter between HRC70 80 and Z2
Depending on the tube used
1 heat pump on 1 pilote Z2
Steel
Copper
Multi-layered
PER-tube
If distance between heat pump and indoor module <10m
53,9 mm
41,8 mm
41,8 mm
41,8 mm
If distance between heat pump and indoor module >10 m and <20 m
63,8 mm
49,6 mm
49,6 mm
49,6 mm
If distance between heat pump and indoor module >20 m and <35 m
72,6 mm
56,8 mm
56,8 mm
56,8 mm
If distance between heat pump and indoor module >35 m and <50 m
72,6 mm
56,8 mm
56,8 mm
56,8 mm
If distance between heat pump and indoor module >50 m and <75 m
78,3 mm
61,6 mm
61,6 mm
61,6 mm
If distance between heat pump and indoor module >75 m and <100 m