THORIX • Low and high water temperature regulation

  • Intuis - Auer
  • Air/water monoblock
  • Accessories

Thorix EVOLUTION is used for the regulation and distribution of a 2nd temperature circuit in the installation. This regulation makes it possible to work with 2 different water temperatures for both floor heating at low water temperature and a high water temperature for, for example, fancoils or radiators. A correct adjustment is obtained in combination with the room thermostat. The module can be used with the Auer monoblock heat pumps that are suitable for this appliance.

The module is equipped with an electronically controlled 3-way mixing valve for the adjustment of the 2 temperature circuits of, for example, radiators and floor heating and this depending on the outside temperature (with outside sensor) and the room temperature (with or without thermostat or interactive room sensor). It is equipped with a motorized 2-way valve that allows the circulation of the water from the heat pump to circuit No. 1 - radiators or floor heating, depending on the room temperature.

Brand

  • Auer - Intuis

Installation

Thorix EVOLUTION must be installed in an open area to allow cooling of its electronic components by means of natural ventilation. The ventilation openings on the bottom and top of the appliance must be free and open at all times. Do not install the device in a small space such as a closed cabinet. The maximum ambient temperature must not exceed 25°C. Allow a clearance of 50 mm on each side of the unit for easy removal of the casing.

Accessories

  • Thermostat for HRC TH HRC70

Applicable indoor units

  • Only to be applied in combination with the DS170 & HRC Premium+ heat pumps

Artikelen

Artikelselectie-assistent
Type
L Gat [mm]
H Gat [mm]
Qv(2Pa) [m³/h]
Qv(10Pa) [m³/h]
Artikelnummer Type L Gat [mm] H Gat [mm] Qv(2Pa) [m³/h] Qv(10Pa) [m³/h] E-shop
E020530200100 GZ60+GZKF+GZKV 200 X 100 200 100 19.30 42.50
E020530200200 GZ60+GZKF+GZKV 200 X 200 200 200 48.30 112.50
E020530300100 GZ60+GZKF+GZKV 300 X 100 300 100 28.50 65.30
E020530300200 GZ60+GZKF+GZKV 300 X 200 300 200 67.50 175.10
E020530300300 GZ60+GZKF+GZKV 300 X 300 300 300 133 289.20
E020530400100 GZ60+GZKF+GZKV 400 X 100 400 100 39 88.20
E020530400200 GZ60+GZKF+GZKV 400 X 200 400 200 107.40 239.10
E020530400300 GZ60+GZKF+GZKV 400 X 300 400 300 192.20 397.70
E020530400400 GZ60+GZKF+GZKV 400 X 400 400 400 291.10 563.80
E020530500100 GZ60+GZKF+GZKV 500 X 100 500 100 47.80 111.40
E020530500200 GZ60+GZKF+GZKV 500 X 200 500 200 141 304.50
E020530500300 GZ60+GZKF+GZKV 500 X 300 500 300 258.40 509.70
E020530500400 GZ60+GZKF+GZKV 500 X 400 500 400 400.10 727
E020530600100 GZ60+GZKF+GZKV 600 X 100 600 100 58.10 134.70
E020530600200 GZ60+GZKF+GZKV 600 X 200 600 200 177.20 371.10
E020530600300 GZ60+GZKF+GZKV 600 X 300 600 300 331.70 625.20
E020530600400 GZ60+GZKF+GZKV 600 X 400 600 400 521.50 897
E020530700100 GZ60+GZKF+GZKV 700 X 100 700 100 86.70 158.20
E020530700200 GZ60+GZKF+GZKV 700 X 200 700 200 216.10 439.10
E020530700300 GZ60+GZKF+GZKV 700 X 300 700 300 412 744.30
E020530700400 GZ60+GZKF+GZKV 700 X 400 700 400 656 1073.30
E020530800100 GZ60+GZKF+GZKV 800 X 100 800 100 79.70 182
E020530800200 GZ60+GZKF+GZKV 800 X 200 800 200 257.70 508.50
E020530800300 GZ60+GZKF+GZKV 800 X 300 800 300 499.30 866.80
E020530800400 GZ60+GZKF+GZKV 800 X 400 800 400 804.80 1257.10
=> Voorraadproduct centraal magazijn behoudens verkoop
=> Voorraadproduct regionale filialen behoudens verkoop

Notes

Power consumption 4 to 70W depending on the speed.
Absorbed current 0.05 to 0.58A depending on the speed.

Notes

A = boiler inlet 3/4"
B = boiler outlet 3/4"
C = mixing circuit outlet 3/4"
D = direct circuit outlet 3/4"
E = mixing circuit return 3/4"
F = direct circuit return 3/4"

Notes

1 = View of protective covers removed
2 = Return sensor to boiler
3 = Boiler inlet sensor
4 = Flow sensor to heating circuit
5 = LTP (floor circuit only)
6 = Electrical supply of the motorized valve
  • brown wire on terminal 3
  • blue wire on terminal 4

Dimensions

Dimensional characteristics
Height286 mm
Width420 mm
Depth260 mm
Hydraulic connections3/4"
Weight10 kg
Maximum installation power18 kW