Vertical ductable dehumidifier
for indoor swimming pools. The
SDA increases comfort and prevents mould growth
and moisture damage to furniture or the building structure. The units have an
epoxy coating to resist chlorine vapours. Optionally, this dehumidifier can be
equipped with a heating coil for a more pleasant indoor climate.
The dehumidifier does not have a built-in humidity probe. Choose from the accessories listed below for a built-in humidity probe RGDD or a remote humidistat HYGR for installation in the swimming pool area.
The "SDA 200 1PH LPHW" is a stock product central warehouse unless sold and has the following options
fitted as standard:
- RGDD Humidity and temperature
sensor Built-in
- HOWA Hot water battery
- KIVM 3 way modulating valve kit (Build-in)
Technical data
|
Moisture removal at 30°C - 80% | l/24h | 73 | 95.2 | 157.1 | 157.1 | 194.3 | 194.3 | Moisture removal at 30°C - 60% | l/24h | 56.6 | 76.5 | 111 | 111 | 145.3 | 145.3 | Moisture removal at 27°C - 60% | l/24h | 49.4 | 68.5 | 99.7 | 99.7 | 127.8 | 127.8 | Moisture removal at 20°C - 60% | l/24h | 34.5 | 50.2 | 66.6 | 66.6 | 90.6 | 90.6 | Nominal input power(1) | kW | 1.4 | 1.83 | 2.22 | 2.22 | 2.84 | 2.84 | Maximum input power(1) | kW | 1.8 | 2 | 2.7 | 3.0 | 3.2 | 3.5 | Electrical post-heater (option) | kW | 3 | 3 | 6 | 4.5 | 6 | 4.5 | Maximum input current(1) | A | 7.1 | 8.1 | 12.6 | 8.1 | 15.5 | 9.5 | Peak current | A | 25 | 38 | 47 | 31 | 66 | 46 | Hot water coil(2) | kW | 7.5 | 8.5 | 13.9 | 13.9 | 15.2 | 15.2 | Partial heat recovery(3) | kW | 1.1 | 1.7 | 2.3 | 2.3 | 3.0 | 3 | Air flow rate | m3/h | 800 | 1000 | 1500 | 1500 | 1800 | 1800 | Available static pressure | Pa | 50÷150 | Refrigerant (GWP) | | R410A (2088) | Refrigerant charge | g (CO2eq-T) | 550 (1.148) | 1100 (2.297) | Sound power(4) | dB(A) | 59 | 61 | 67 | 67 | 69 | 69 | Sound pressure level(5) | dB(A) | 52 | 54 | 60 | 60 | 62 | 62 | Power supply | V/Ph/Hz | 230/1/50 | 400/3+N/50 | 230/1/50 | 400/3+N/50 |
Performances are calculated with low fan speed and are referred to the following conditions: - (1) Without electrical heater
- (2) Room temperature 30°C, water temperature 80/70°C, compressor OFF
- (3) Room temperature 30°C/80%, water temperature 27/32°C, compressor OFF
- (4) Sound Power level according to ISO 9614 fan with available static pressure 50 Pa
- (5) Sound Pressure level measured at 1 meter from the unit in free field conditions according with ISO 9614, fan
with available static pressure 50 Pa
Dimensions
|
SDA 75 | F1 | 800 | 800 | 400 | 85 | SDA 100 | F1 | 800 | 800 | 400 | 90 | SDA 150/153 | F2 | 1000 | 1060 | 550 | 130 | SDA 200/203 | F2 | 1000 | 1060 | 550 | 135 |
Accessories
|
Hot water coil (LPHW) | HOWA.75 | HOWA.76 | Electrical post-heating battery 3 kW (230/1/50) | HOEL.30 | - | - | - | - | Electrical post-heating battery 4,5 kW (230/1/50) | - | - | - | HOEL.45 | - | HOEL.45 | Electrical post-heating battery 6 kW (230/1/50) | - | - | HOEL.62 | - | HOEL.62 | - | Built-in electronic temperature/humidity sensor | RGDD.05 | Mechanical humidistat | HYGR.20 | Remote control panel | PCRL.10 | Serial card RS485-MODBUS | INSE.10 | Built-in 3-way valve | KIVM.75 | KIVM.76 | Partial heat recovery watercondensor CU-NI | RP01.75 | RP01.10 | RP01.20 | AC fan with available static pressure up to 150 Pa | Standard | EC fan with available static pressure up to 300 Pa | V1CE.10 | V1CE.20 | Rubber vibration dampers | KAVG.20 |
|