- 2 lengths - 1,5 and 2 meter
- Industrial gates
- Air flow: 4000 - 8600 m³/h
- 7,5-meter range*
- Highly efficient axial fans with protection degree IP54
- Horizontal and vertical mounting
- Mounting componentes as standard
- BMS connection possible
- Painted white, RAL 9016
* Vertical range of isothermal stream (at velocity boundary equal to 3 m/s)
Technical data
|
Power supply | [V/Hz] | 230/50 | 230/50 | 3x400/50 | 230/50 | 230/50 | 3x400/50 | Power consumption | [kW] | 0.64 | 0.64 | 12.6 | 0.96 | 0.96 | 21 | Current consumption | [A] | 2.8 | 2.8 | 17 | 4.2 | 4.2 | 29 | Heating capacity | [kW] | 22.9 | - | 11 | 24.9 | - | 20 | IP | | 54 | 54 | 54 | 54 | 54 | 54 | Connection | ["] | 3/4" | - | - | 3/4" | - | - | Air flow | [m³/h] | 6200 | 6500 | 6300 | 8100 | 8600 | 8200 | Sound level (1) | [dB(A)] | 54 | 54 | 56 | 56 | 56 | 56 | Max. heating water temp. | [°C] | 130 | - | - | 130 | - | - | Max. operating pressure | [MPa] | 1.6 | - | - | 1.6 | - | - | Air temperature rise (2) | (∆T) [°C] | 12 | - | 12 | 12 | - | 12 | Weight | [kg] | 47.4 | 43 | 49.8 | 62 | 58 | 67 | Weight of unit filled with water | [kg] | 49.7 | - | - | 64.3 | - | - | (1) Acoustic pressure level measured for optimum installation height, on second step of efficiency, in the room with medium capability of sound absorption, capacity 500 m³/h, at distance of 3 m from the unit | (2) For INDUSTRY-W at inlet/outlet water temperature 90/70°C and inlet air temperature 10°C / for INDUSTRY-E at inlet air temperature 10°C |
|