OPTIGO 5 • HVAC controllers

Preprogrammed, easy to configure HVAC controller with numeric/graphic background illuminated display

Brand

  • Regin

Application

  • Temperature control
  • CO2 - control
  • Humidity control
  • Pressure control
  • Pressure control with outdoor compensation

Specifications

  • Supply voltage: 24 V AC
  • 1 analogue input for PT1000
  • 1 digital input
  • 1 universal input 0 - 10 V DC or digital
  • 2 analogue ouputs 0 - 10 V DC

Mounting

  • DIN-rail

Accessoires

  • Transfo 230 / 24 V AC, type TRAFO 15/D
  • Duct temperature sensor, type TG-KH/PT1000 / TG-K3/PT1000
  • Room temperature sensor, type TG-R5/PT1000
  • Outdoor temperature sensor, type TG-UH3/PT1000
  • Pressure transmitter, type DMD
  • Pressure switch, type DTV
  • CO2 transmitter, type WOX/E(-D) (room) / DOX-E (duct)
  • Humidity transmitter, type HRTN (room) / DTTH (duct)

Technical data

  • Power consumpition: 6 VA
  • IP 20

Function

  • Temperature control : the temperature at the sensor is kept at the setpoint value by controlling output signals on AO1 and AO2. A single PI control loop is used. The output AO1 can by configured as : heating / cooling / changeover, the output AO2 can by configured as : not used / cooling / heating / damper
  • CO2 control : The CO2-value at the sensor is kept at the setpoint value by controlling the ouput signal AO1. A single PI control loop is used. The output signal will increase when the CO2-value rises above the setpoint value
  • Humidity control : The humidity at the sensor is kept at the setpoint value by controlling the output signals on AO1 and AO2. AO1 is used for humidification, AO2 for dehumidification. A single PI loop is used. Humidification and dehumidification can be used simultaneously, a neutral zone can be set between.
  • Pressure control : The pressure at the sensor is kept at the setpoint value by controlling output signal AO1. A single PI control loop is used. The output signal will increase when the pressure signal falls below the setpoint value.
  • Pressure control with outdoor compensation : The pressure at the sensor is kept at the setpoint value by controlling the output signal on AO1. The setpoint is automatically adjusted according to the outdoor temperature. A single loop PI control is used. The output signal will increase when the pressure signal falls below the setpoint value. the setpoint value follows a settable pressure-to-outdoor temperature relation

Settings

  • Temperature setpoints :
  1. Temperature: -20 to 40°C
  2. Hysteresis: 0 to 10°C
  3. P-band: 0 to 99 s
  4. I-time: 0 to 999 s
  5. Min-limit damper: 0 to 99%
  • Other settings
  1. CO2 setpoint: 0 to 5000 ppm (settable range correnponds the range of the sensor)
  2. Humidity setpoint: 0 to 100 %
  3. Pressure setpoint: 0 to 500 kPa (settable range corresponds the range of the sensor)
  4. P-band: 0 to 100 %
  5. I-time: 0 to 990 s
  6. Outdoor compensation, start: -30 to 50°C
  7. Pressure at -20°C outdoor temp.: 50 to 500 kPa