OPTIGO 10 • HVAC controllers

Preprogrammed, easy to configure HVAC controller with numeric/graphic background illuminated display, with built-in week scheduler

Brand

  • Regin

Application

  • Supply air temperature control
  • Supply air temperature control with outdoor compensation
  • Exhaust air / room temperature control with cascade function
  • Radiator control with outdoor compensation
  • Tap hot water control

Specifications

  • Supply voltage: 24 V AC (OPTIGO 10) / 230 V AC (OPTIGO 10-230V)
  • 2 analogue input for PT1000
  • 2 digital input
  • 1 universal input PT1000 or digital
  • 2 analogue ouputs 0 - 10 V DC
  • 2 digital outputs triac controlled 24 V AC - 0,5 A
  • 1 digital output change-over relay 230 V AC - 5 A

Mounting

  • DIN-rail

Accessoires

  • Transfo 230 / 24 V AC, Type TRAFO 15/D (only for OPTIGO 10)
  • Duct temperature sensor, Type TG-KH/PT1000 / TG-K3/PT1000
  • Room temperature sensor, Type TG-R5/PT1000
  • Outdoor temperature sensor, Type TG-UH/PT1000
  • Clamp-on temperature sensor, Type TG-AH3/PT1000
  • Pressure switch, Type DTV

Technical data

  • Power consumpition: 6 VA
  • IP 20

Function

  • Supply air temperature control : The supply air temperature is kept at the setpoint value by controlling the ouput signals on AO1 and AO2. A single PI control loop is used
  • Supply air temperature control with outdoor compensation : The supply air temperature is kept at the setpoint value by controlling the ouput signals on AO1 and AO2. A single PI control loop is used. The setpoint is automatically adjusted according to the outdoor temperature
  • Exhaust air / room temperature control with cascade function : An offset in room temperature will adjust the supply air temperature setpoint so as to eliminate the room temperature offset. One PI and one P control loop are used. The supply air temperature can be minimum and maximum limited
  • Radiator control with outdoor compensation : The water temperature setpoint is changed according to the outdoor temperature. A single PI control loop is used. A room temperature sensor can be added to give corrective action if the room temperature differs from the setpoint
  • Tap hot water control : The water temperature is kept constant by controlling the output signal on AO1. A single PID control loop is used

Settings

  • Setpoint supply air temperature: 10 to 40°C
  • Setpoint room temperature: 10 to 40°C
  • Setpoint tap hot water: 10 to 80°C
  • P-band: 0 to 99°C
  • I-time: 0 to 990 s
  • D-time: 0 to 99
  • Cascade factor: 0 to 99°C
  • Damper min. limit: 0 to 99
  • Start outdoor compensation: -30 to 50°C