PRODUCTEN
EShop-nummer
Wachtwoord
Welcome to CAIROX BELGIUM

NM A-(S) • Actuators 10Nm

Servomotor for air volume control dampers of up to 2 m² depending on the type of air valve and the pressure on the valves. Simple direct mounting on the damper axe with a universal spindle clamp, supplied with an anti-rotation strap to prevent the actuator from rotating.

Type S: with integrated 0-100% auxiliary switch, for adjustable signalization.

Brand

  • Belimo

Application

  • Dampers

Specifications

  • Torque 10 Nm
  • Nominal Voltage NM 230A-(S) 230 V AC
  • Nominal voltage NM 24A-(S) 24 V AC/DC
  • Control: open-close or 3-point

Accessoires

  • Auxiliary switchs, type S1A (1) or S2A (2)
  • Shaft extension, type AV8-25

Artikelen

Article selection assistant
Type
Type
Article number Type Type E-shop
I040102201000 RNFLA 200 200
I040102253000 RNFLA 250 250
I040102302000 RNFLA 300 300
I040102353000 RNFLA 350 350
I040102403000 RNFLA 400 400
I040102455000 RNFLA 450 450
I040102503000 RNFLA 500 500

Technical data

  • Power consumption:
  1. In operation: 2,5 W @ nominal torque NM 230A-(S) / 1,5 W @ nominal torque NM 24A-(S)
  2. At rest: 0.6 W NM 230A-(S) / 0.2 W NM 24A-(S)
  3. For wire sizing: 6 VA NM 230A-(S) / 4 VA NM 24A-(S)
  • Direction of rotation: reversible with switch 0 or 1
  • Manual override: gearing latch disengaged with pushbutton, self-resetting
  • Angle of rotation: max. 95° , limited on both sides by means of adjustable, mechanical end stops. The actuator is overload proof; requires no limit switches and automatically stops when the end stop is reached
  • Running time: 150 s
  • Sound power level: max. 35 dB (A)
  • Position indication: mechanical, pluggable

  • Degree of protection: IP54 in any mounting position

Wiring diagram

Electrical diagram

Text for tender

Kopiëren
  • The servomotor shall be of the open-close type with a torque of 10 Nm for direct mounting on the damper axe. With integrated 0-100% auxiliary switch (Type S). With reversible direction of rotation, angle max 95° with mechanical end stops. Protection class II totally insulated, IP 54 in any mounting position EMC: CE according to 89/336/EEC and LVD 73/23/EEC.
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be