The actuator has been designed for use in stationary heating, ventilation and
air-conditioning systems and is not allowed to be used outside the specified field
of application, especially in aircraft or in any other airborne means of transport.
Technical data
Functional data
- Actuating force: 500 N
- Manual override:Gear disengagement with push-button, can be locked
- Nominal stroke: 15 mm
- Actuating time: 150 s / 15 mm
- Sound power level motor max.: 45 dB (A)
- Position indication: Mechanical 5 … 15 mm stroke
Safety
- Protection class IEC/EN: II Protective insulated
- Degree of protection IEC/EN: IP54
- EMC: CE in accordance with 2004/108/EC
- Certification IEC/EN: Certified to: IEC/EN 60730-1 and IEC/EN 60730-2-14
- Mode of operation: Type 1
- Rated current voltage supply: 4 kV
- Control pollution degree: 3
- Ambient temperature: 0°C ... 50°C
- Non-operating temperature: -40°C ... 80°C
- Ambient humidity: 95% r.h., non-condensing
- Maintenance: Maintenance-free
- Weight: 1.320 kg
Technical data
|
LV24A-TPC | 24 | 500 | 150 | on/off | 15 | LV24A-SR-TPC | 24 | 500 | 150 | modulating 0-10V | 15 | LV230A-TPC | 230 | 500 | 150 | on/off | 15 |
|