The glove valve has been designed for use in stationary heating, ventilation and
air-conditioning systems and is not allowed to be used outside the specified field
of application, especially in aircraft or in any other airborne means of transport.
Specifications
The globe valve is adjusted by a globe valve actuator. The actuators are connected by a commercially available modulating or 3-point control system and move the valve cone, which acts as a throttling device, into the opening position dictated by the positioning signal. Coupling pipes not included!
Articles
Article selection assistant
Type
Cooling capacity [kW]
Heating Capacity* [kW]
# pipes
AC or EC engine
Horizontal or vertical
Hydraulic connection
Article number
Type
Cooling capacity [kW]
Heating Capacity* [kW]
# pipes
AC or EC engine
Horizontal or vertical
Hydraulic connection
E-shop
J035530012010
UTV-10/L/2P
3.83
5.02
2
AC
Vertical
Left
J035530012020
UTV-20/L/2P
7.05
8.61
2
AC
Vertical
Left
J035530012030
UTV-30/L/2P
9.2
11.3
2
AC
Vertical
Left
J035530012040
UTV-40/L/2P
10.6
12.94
2
AC
Vertical
Left
J035530012050
UTV-50/L/2P
13.1
16.99
2
AC
Vertical
Left
J035530013010
UTV-10/R/2P
3.83
5.02
2
AC
Vertical
Right
J035530013020
UTV-20/R/2P
7.05
8.61
2
AC
Vertical
Right
J035530013030
UTV-30/R/2P
9.2
11.3
2
AC
Vertical
Right
J035530013040
UTV-40/R/2P
10.6
12.94
2
AC
Vertical
Right
J035530013050
UTV-50/R/2P
13.1
16.99
2
AC
Vertical
Right
J035530014110
UTV-10/L/4P
3.6
4.18
4
AC
Vertical
Left
J035530014120
UTV-20/L/4P
7.00
7.01
4
AC
Vertical
Left
J035530014130
UTV-30/L/4P
9.01
9.16
4
AC
Vertical
Left
J035530014140
UTV-40/L/4P
9.57
10.60
4
AC
Vertical
Left
J035530014150
UTV-50/L/4P
13.63
12.65
4
AC
Vertical
Left
J035530015010
UTV-10/R/4P
3.6
4.18
4
AC
Vertical
Right
J035530015020
UTV-20/R/4P
7.00
7.01
4
AC
Vertical
Right
J035530015030
UTV-30/R/4P
9.01
9.16
4
AC
Vertical
Right
J035530015040
UTV-40/R/4P
9.57
10.60
4
AC
Vertical
Right
J035530015050
UTV-50/R/4P
13.63
12.65
4
AC
Vertical
Right
J035530022010
UTC-10/L/2P
3.83
5.02
2
AC
Horizontal
Left
J035530022020
UTC-20/L/2P
7.05
8.61
2
AC
Horizontal
Left
J035530022030
UTC-30/L/2P
9.20
11.33
2
AC
Horizontal
Left
J035530022040
UTC-40/L/2P
10.60
12.94
2
AC
Horizontal
Left
J035530022050
UTC-50/L/2P
13.10
16.99
2
AC
Horizontal
Left
J035530023010
UTC-10/R/2P
3.83
5.02
2
AC
Horizontal
Right
J035530023020
UTC-20/R/2P
7.05
8.61
2
AC
Horizontal
Right
J035530023030
UTC-30/R/2P
9.20
11.33
2
AC
Horizontal
Right
J035530023040
UTC-40/R/2P
10.60
12.94
2
AC
Horizontal
Right
J035530023050
UTC-50/R/2P
13.10
16.99
2
AC
Horizontal
Right
J035530032010
UTC-10/L/4P
3.60
4.18
4
AC
Horizontal
Left
J035530032020
UTC-20/L/4P
7
7.01
4
AC
Horizontal
Left
J035530032030
UTC-30/L/4P
9.01
9.16
4
AC
Horizontal
Left
J035530032040
UTC-40/L/4P
9.57
10.60
4
AC
Horizontal
Left
J035530032050
UTC-50/L/4P
13.63
12.65
4
AC
Horizontal
Left
J035530033010
UTC-10/R/4P
3.60
4.18
4
AC
Horizontal
Right
J035530033020
UTC-20/R/4P
7
7.01
4
AC
Horizontal
Right
J035530033030
UTC-30/R/4P
9.01
9.16
4
AC
Horizontal
Right
J035530033040
UTC-40/R/4P
9.57
10.60
4
AC
Horizontal
Right
J035530033050
UTC-50/R/4P
13.63
12.65
4
AC
Horizontal
Right
*According to Eurovent at highest speed 0Pa
Specifications
DN [mm]
Rp [Inch]
Kvs [m³/h]
ps [kPa]
Stroke [mm]
H411B
15
1/2
0,63
1600
15
H412B
15
1/2
1
1600
15
H413B
15
1/2
1,6
1600
15
H414B
15
1/2
2,5
1600
15
H415B
15
1/2
4
1600
15
H420B
20
3/4
6,3
1600
15
H425B
25
1
10
1600
15
H432B
32
1 1/4
16
1600
15
Technical data
Functional data
Media: Cold and hot water, water with glycol up to max. 50% vol
Medium temperature: 5°C ... 120 °C
Leakage rate: Leakage Class III (DIN EN 1349 and DIN EN 60534-4)
Pipe connectors: External thread in accordance to ISO 228
Closing point: Top
Installation position: Upright to horizontal (in relation to the stem)