This site uses cookies and related technologies, as described in our privacy policy, for purposes that may include site operation, analytics, enhanced user experience, or advertising. You may choose to consent to our use of these technologies, or manage your own preferences.
The glove valve has been designed for use in stationary heating, ventilation and
air-conditioning systems and is not allowed to be used outside the specified field
of application, especially in aircraft or in any other airborne means of transport.
Specifications
The globe valve is adjusted by a globe valve actuator. The actuators are connected by a commercially available modulating or 3-point control system and move the valve cone, which acts as a throttling device, into the opening position dictated by the positioning signal. Coupling pipes not included!
Artikelen
Article selection assistant
Type
Length [mm]
Width [mm]
Height [mm]
Max. load [kg]
Packing [pieces]
Article number
Type
Length [mm]
Width [mm]
Height [mm]
Max. load [kg]
Packing [pieces]
E-shop
J050106060000
MPRH 600
600
200
150
250
1
J050106120000
MPRH 1200
1200
200
150
500
1
=> Stock product central warehouse, except sales
=> Stock product local warehouses, except sales
=> Article with a volume discount
1) MPRH 600 en MPRH 1200: All necessary screws are delivered with the mounting bloc: 2 M10x25 bolts, 2 M10 wrenches & 2 M10x20 washers
SLNB-GT M8: bolts with serrated sliding nuts
Specifications
DN [mm]
Rp [Inch]
Kvs [m³/h]
ps [kPa]
Stroke [mm]
H411B
15
1/2
0,63
1600
15
H412B
15
1/2
1
1600
15
H413B
15
1/2
1,6
1600
15
H414B
15
1/2
2,5
1600
15
H415B
15
1/2
4
1600
15
H420B
20
3/4
6,3
1600
15
H425B
25
1
10
1600
15
H432B
32
1 1/4
16
1600
15
Technical data
Functional data
Media: Cold and hot water, water with glycol up to max. 50% vol
Medium temperature: 5°C ... 120 °C
Leakage rate: Leakage Class III (DIN EN 1349 and DIN EN 60534-4)
Pipe connectors: External thread in accordance to ISO 228
Closing point: Top
Installation position: Upright to horizontal (in relation to the stem)