This site uses cookies and related technologies, as described in our privacy policy, for purposes that may include site operation, analytics, enhanced user experience, or advertising. You may choose to consent to our use of these technologies, or manage your own preferences.
The glove valve has been designed for use in stationary heating, ventilation and
air-conditioning systems and is not allowed to be used outside the specified field
of application, especially in aircraft or in any other airborne means of transport.
Specifications
The globe valve is adjusted by a globe valve actuator. The actuators are connected by a commercially available modulating or 3-point control system and move the valve cone, which acts as a throttling device, into the opening position dictated by the positioning signal. Coupling pipes not included!
Articles
Article selection assistant
Type
Length [mm]
Slots
Connection size
Article number
Type
Length [mm]
Slots
Connection size
E-shop
A04650T120625
GYP-P-LINE - 1 - L= 625 MM - A
625
1
A
A04650T120A00
GYP-P-LINE - 1 - L=1000 MM - A
1000
1
A
A04650T120C50
GYP-P-LINE - 1 - L=1250 MM - A
1250
1
A
A04650T220625
GYP-P-LINE - 2 - L= 625 MM - B
625
2
B
A04650T220A00
GYP-P-LINE - 2 - L=1000 MM - B
1000
2
B
A04650T220C50
GYP-P-LINE - 2 - L=1250 MM - B
1250
2
B
A04650T320625
GYP-P-LINE - 3 - L= 625 MM - C
625
3
C
A04650T320A00
GYP-P-LINE - 3 - L=1000 MM - C
1000
3
C
A04650T320C50
GYP-P-LINE - 3 - L=1250 MM - C
1250
3
C
=> Stock product central warehouse, except sales
Specifications
DN [mm]
Rp [Inch]
Kvs [m³/h]
ps [kPa]
Stroke [mm]
H411B
15
1/2
0,63
1600
15
H412B
15
1/2
1
1600
15
H413B
15
1/2
1,6
1600
15
H414B
15
1/2
2,5
1600
15
H415B
15
1/2
4
1600
15
H420B
20
3/4
6,3
1600
15
H425B
25
1
10
1600
15
H432B
32
1 1/4
16
1600
15
Technical data
Functional data
Media: Cold and hot water, water with glycol up to max. 50% vol
Medium temperature: 5°C ... 120 °C
Leakage rate: Leakage Class III (DIN EN 1349 and DIN EN 60534-4)
Pipe connectors: External thread in accordance to ISO 228
Closing point: Top
Installation position: Upright to horizontal (in relation to the stem)