Grilles en aluminium anodisé avec ailettes fixes et pas de 12.5 mm, déflexion de 0°
- ALG-0, 800, 200 + CCN + DWN + REW
Explication
ALG-0 = Type de grille
800 = Longueur (voir tableau)
200 = Hauteur (voir tableau)
Accessoires (en option)
CCN = Cadre de montage
DWN = Registre de réglage du débit
REW = Caisson
Sélection rapide
|
|
|
|
Q | Ak | 0.0021 | 0.0083 | 0.0145 | 0.0206 | 0.0268 | 0.0361 | 0.0392 | 0.0453 | 0.0515 | 0.0638 | 0.0823 | 0.1008 | 0.1132 | 0.1379 | 0.1749 | 50 | Vk | 6.6 | 1.7 | | | | | | | | | | | | | | X0,25 | 5.7 | 3.3 | | | | | | | | | | | | | | Ps | 32 | 2 | | | | | | | | | | | | | | Lw(A) | 30 | <20 | | | | | | | | | | | | | | 100 | Vk | | 3.3 | 1.9 | 1.3 | 1 | | | | | | | | | | | X0,25 | | 6.1 | 4.8 | 4.2 | 3.8 | | | | | | | | | | | Ps | | 8 | 3 | 1 | 1 | | | | | | | | | | | Lw(A) | | 24 | <20 | <20 | <20 | | | | | | | | | | | 150 | Vk | | 5 | 2.9 | 2 | 1.6 | 1.2 | 1.1 | | | | | | | | | X0,25 | | 8.8 | 6.9 | 6 | 5.4 | 4.8 | 4.6 | | | | | | | | | Ps | | 19 | 6 | 3 | 2 | 1 | 1 | | | | | | | | | Lw(A) | | 32 | 25 | <20 | <20 | <20 | <20 | | | | | | | | | 200 | Vk | | 6.7 | 3.8 | 2.7 | 2.1 | 1.5 | 1.4 | 1.2 | 1.1 | | | | | | | X0,25 | | 11.5 | 9 | 7.8 | 7 | 6.2 | 6 | 5.6 | 5.4 | | | | | | | Ps | | 33 | 11 | 6 | 3 | 2 | 2 | 1 | 1 | | | | | | | Lw(A) | | 38 | 30 | 25 | 22 | <20 | <20 | <20 | <20 | | | | | | | 300 | Vk | | | 5.7 | 4 | 3.1 | 2.3 | 2.1 | 1.8 | 1.6 | 1.3 | 1 | | | | | X0,25 | | | 13.2 | 11.4 | 10.2 | 9 | 8.7 | 8.1 | 7.7 | 7.1 | 6.4 | | | | | Ps | | | 24 | 12 | 7 | 4 | 4 | 3 | 2 | 1 | 1 | | | | | Lw(A) | | | 38 | 33 | 30 | 25 | 24 | 22 | 21 | <20 | <20 | | | | | 400 | Vk | | | 7.7 | 5.4 | 4.1 | 3.1 | 2.8 | 2.5 | 2.2 | 1.7 | 1.4 | 1.1 | | | | X0,25 | | | 17.4 | 15 | 13.3 | 11.7 | 11.3 | 10.6 | 10.1 | 9.2 | 8.3 | 7.6 | | | | Ps | | | 42 | 21 | 13 | 7 | 6 | 5 | 4 | 2 | 1 | 1 | | | | Lw(A) | | | 44 | 39 | 35 | 31 | 30 | 28 | 26 | 23 | <20 | <20 | | | | 600 | Vk | | | | | 6.2 | 4.6 | 4.3 | 3.7 | 3.2 | 2.6 | 2 | 1.7 | 1.5 | 1.2 | | X0,25 | | | | | 19.7 | 17.3 | 16.7 | 15.6 | 14.8 | 13.5 | 12.1 | 11.1 | 10.5 | 9.7 | | Ps | | | | | 28 | 16 | 13 | 10 | 8 | 5 | 3 | 2 | 2 | 1 | | Lw(A) | | | | | 43 | 39 | 38 | 36 | 34 | 31 | 27 | 25 | 23 | 20 | | 800 | Vk | | | | | | 6.2 | 5.7 | 4.9 | 4.3 | 3.5 | 2.7 | 2.2 | 2 | 1.6 | 1.3 | X0,25 | | | | | | 22.8 | 22 | 20.6 | 19.5 | 17.8 | 15.9 | 14.5 | 13.8 | 12.7 | 11.5 | Ps | | | | | | 28 | 24 | 18 | 14 | 9 | 6 | 4 | 3 | 2 | 1 | Lw(A) | | | | | | 44 | 43 | 41 | 39 | 37 | 33 | 30 | 29 | 26 | 23 | 1000 | Vk | | | | | | 7.7 | 7.1 | 6.1 | 5.4 | 4.4 | 3.4 | 2.8 | 2.5 | 2 | 1.6 | X0,25 | | | | | | 28.4 | 27.3 | 25.6 | 24.2 | 22 | 19.7 | 18 | 17.1 | 15.7 | 14.2 | Ps | | | | | | 43 | 36 | 27 | 21 | 14 | 9 | 6 | 5 | 3 | 2 | Lw(A) | | | | | | 49 | 48 | 46 | 44 | 41 | 37 | 35 | 33 | 30 | 27 | 1200 | Vk | | | | | | | | 7.4 | 6.5 | 5.2 | 4.1 | 3.3 | 2.9 | 2.4 | 1.9 | X0,25 | | | | | | | | 30.6 | 28.9 | 26.3 | 23.5 | 21.5 | 20.4 | 18.7 | 16.9 | Ps | | | | | | | | 39 | 30 | 20 | 12 | 8 | 7 | 5 | 3 | Lw(A) | | | | | | | | 49 | 47 | 44 | 41 | 38 | 36 | 34 | 30 | 1600 | Vk | | | | | | | | | | 7 | 5.4 | 4.4 | 3.9 | 3.2 | 2.5 | X0,25 | | | | | | | | | | 34.9 | 31.1 | 28.4 | 27 | 24.7 | 22.3 | Ps | | | | | | | | | | 35 | 21 | 14 | 12 | 8 | 5 | Lw(A) | | | | | | | | | | 50 | 46 | 44 | 42 | 39 | 36 | 2000 | Vk | | | | | | | | | | | 6.8 | 5.5 | 4.9 | 4 | 3.2 | X0,25 | | | | | | | | | | | 38.7 | 35.4 | 33.6 | 30.8 | 27.7 | Ps | | | | | | | | | | | 33 | 22 | 18 | 12 | 8 | Lw(A) | | | | | | | | | | | 51 | 48 | 46 | 44 | 40 |
Symboles et spécifications
LxH = Longueur L et hauteur H en mm
Q = Débit d’air en m³/h
Ak = Surface effective (passage libre) en m²
Vk = Vitesse effective à travers de la grille en m/s
X0.25 = Portée horizontale en m à une vitesse finale Vt de 0,25m/s
Ps = Perte de pression statique de la grille en Pa
Lw(A) = Puissance acoustique de la grille en dB(A)
Les portées X0.25 sont données sans inclinaison des ailettes et à une vitesse finale Vt de 0,25 m/s. Elles sont données à une distance de placement de la grille sous plafond de 300 mm sans obstacles. Lorsque la grille est montée à une distance de 400 à 600 mm par rapport au plafond, une déviation horizontale de 15 ° vers le plafond est conseillée. Si la grille est montée à une distance de plus de 600 mm du plafond, la portée de la veine d’air X0.25 deviendra plus petite suite à l’absence de l’effet coanda. Dans ces cas, et pour toutes les autres exigences particulières, veuillez contacter notre bureau d'étude.
Les valeurs sont données en condition isothermique de l'air. Les portées pour des conditions en refroidissement à -11K doivent être recalculées en divisant les valeurs de X0.25 par le facteur 1,1. En chauffage à Dt 11K les valeurs doivent être recalculées en multipliant X0.25 par le facteur 1,1.
La distance conseillée de plusieurs grilles dans le même mur doit être supérieure à 1/3 de la portée X0.25 (exclusif dispersion)
Les pertes de pression Ps sont données pour des grilles sans registre ou avec registre totalement ouvert.
Les puissances acoustiques Lw(A) sont données pour des grilles sans registre ou avec registre totalement ouvert sans atténuation de la chambre. Les puissances acoustiques inférieures à 20 dB(A) sont mentionnées comme "<20" dans les tableaux.
Placement
|