Smoke exhaust roof unit 400°C/2h with motor outside of the airflow and horizontal discharge
RFV-P 28/1 4M F400/120Explanation:
RFV-P = Type of fan
28/1 = Size
4 = Number of poles
M = Type of motor (monophase), T = triphase
F400/120 = Suitable for smoke exhaust 400°C/120 min.
Air performance data
|
|
RFV-P 28/1 4M/4T | 1700 | 1050 | - | - | - | - | - | - | RFV-P 31/1 4M/4T | 2500 | 2000 | 300 | - | - | - | - | - | RFV-P 31/1 6T | 1200 | | - | - | - | - | - | - | RFV-P 35/1 4M/4T | 3800 | 3250 | 2500 | - | - | - | - | - | RFV-P 35/1 6T | 2050 | - | - | - | - | - | - | - | RFV-P 45/1 4M/4T | 6100 | 5600 | 5000 | 2900 | - | - | - | - | RFV-P 45/1 6T | 3600 | 2400 | - | - | - | - | - | - | RFV-P 50/2 4T | 8575 | 8000 | 7350 | 6675 | 5150 | 4300 | - | - | RFV-P 50/2 6T | 5250 | 4150 | - | - | - | - | - | - | RFV-P 56/2 4T | 12200 | 11650 | 10950 | 10200 | 9300 | 8300 | 6900 | 4900 | RFV-P 56/2 6T | 7500 | 6400 | 4900 | - | - | - | - | - | RFV-P 63/3 6T | 13000 | 11900 | 10800 | 9400 | 6800 | - | - | - | RFV-P 71/4 6T | 21000 | 20000 | 18750 | 17000 | 15250 | 12500 | - | - | RFV-P 80/4 6T | 28500 | 27250 | 26000 | 24250 | 22500 | 20500 | 17750 | 13500 | RFV-P 90/4 6T | - | - | 33500 | 32000 | 30250 | 28000 | 25500 | 22000 |
Selection curves
Technical data
|
RFV-P 28/1 4M | 1x230 | 0.25 | 2 | TSC-1-22 | 40* / 400** | -20 | 1500 | RFV-P 31/1 4M | 1x230 | 0.25 | 2 | TSC-1-22 | 40* / 400** | -20 | 1500 | RFV-P 35/1 4M | 1x230 | 0.37 | 2.7 | TSC-1-40 | 40* / 400** | -20 | 1500 | RFV-P 45/1 4M | 1x230 | 0.75 | 4.7 | - | 40* / 400** | -20 | 1500 | RFV-P 28/1 4T | 3x230/400 | 0.25 | 0.7 | FIS-4420E-0.75-B | 40* / 400** | -20 | 1500 | RFV-P 31/1 4T | 3x230/400 | 0.25 | 0.7 | FIS-4420E-0.75-B | 40* / 400** | 20 | 1500 | RFV-P 31/1 6T | 3x230/400 | 0.18 | 0.7 | FIS-4420E-0.75-B | 40* / 400** | -20 | 1000 | RFV-P 35/1 4T | 3x230/400 | 0.37 | 0.7 | FIS-4420E-0.75-B | 40* / 400** | -20 | 1500 | RFV-P 35/1 6T | 3x230/400 | 0.18 | 1 | FIS-4420E-0.75-B | 40* / 400** | -20 | 1000 | RFV-P 45/1 4T | 3x230/400 | 0.75 | 1.7 | FIS-4420E-0.75-B | 40* / 400** | -20 | 1500 | RFV-P 45/1 6T | 3x230/400 | 0.37 | 1 | FIS-4420E-0.75-B | 40* / 400** | -20 | 1000 | RFV-P 50/2 4T | 3x230/400 | 1.1 | 2.4 | FIS-4420E-1.5-B | 40* / 400** | -20 | 1500 | RFV-P 50/2 6T | 3x230/400 | 0.37 | 1 | FIS-4420E-0.75-B | 40* / 400** | -20 | 1000 | RFV-P 56/2 4T | 3x230/400 | 2.2 | 4.7 | FIS-4420E-2.2-B | 40* / 400** | -20 | 1500 | RFV-P 56/2 6T | 3x230/400 | 0.75 | 2 | FIS-4420E-0.75-B | 40* / 400** | -20 | 1000 | RFV-P 63/3 6T | 3x230/400 | 1.5 | 3.7 | FIS-4420E-1.5-B | 40* / 400** | -20 | 1000 | RFV-P 71/4 6T | 3x230/400 | 3 | 6.9 | FIS-4420E-4.0-B | 40* / 400** | -20 | 1000 | RFV-P 80/4 6T | 3x230/400 | 5.5 | 12.8 | FIS-4420E-5.5-B | 40* / 400** | -20 | 1000 | RFV-P 90/4 6T | 3x230/400 | 7.5 | 14.8 | FIS-4420E-7.5-B | 40* / 400** | -20 | 1000 |
- SC = Speed controller
- Tm = Maximum air temperature
- * Maximum air temperature in continuous operation
- ** Maximum air temperature for smoke exhaust
- To = Minimum operating temperature
Dimensions
|
|
RFV-P 28/1 | 550 | 552 | 566 | 500 | 30 | 228 | 210 | 175 | 29 | RFV-P 31/1 | 550 | 552 | 566 | 500 | 30 | 256 | 210 | 175 | 33 | RFV-P 35/1 | 550 | 552 | 566 | 500 | 30 | 289 | 210 | 175 | 35 | RFV-P 45/1 | 550 | 552 | 640 | 500 | 30 | 366 | 210 | 175 | 40 | RFV-P 50/2 | 680 | 701 | 785 | 614 | 30 | 412 | 275 | 224 | 43 | RFV-P 56/2 | 680 | 701 | 785 | 614 | 30 | 463 | 275 | 224 | 78 | RFV-P 63/3 | 840 | 856 | 915 | 760 | 40 | 513 | 340 | 290 | 122 | RFV-P 71/4 | 1050 | 1086 | 1200 | 950 | 40 | 577 | 475 | 385 | 204 | RFV-P 80/4 | 1050 | 1086 | 1200 | 950 | 40 | 650 | 475 | 385 | 215 | RFV-P 90/4 | 1050 | 1086 | 1200 | 950 | 40 | 732 | 475 | 385 | 295 |
|